Notifier CFP-600-E - Control Panel Wiring; Wiring Diagram Overview

Notifier CFP-600-E
33 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Automatic Release Channel Management
Page 20 Installation and Operating Manual CFP-600-Prog-5.VP
NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG
YES NO
NO
NO
FIRST ALARM
PREALARM LED= FLASHING
PREALARM RELAY= ON
BUZZER= STEADY SOUND
INHIBITION?
RELEASE INHIBITION LED= FLASHING
SIGNAL SILENCE?
PREALARM LED= ON
PREALARM RELAY= OFF
BUZZER= intermittent sound
Release Inhibition LED=Flashing
Silenced control LED= ON
SECOND ALARM
ALARM LED= Flashing
ALARM RELAY= ON
SOUNDER RELAY= ON
EVACUATION RELAY= ON
EVACUATION LED= ON
BUZZER= Steady sound
Release Inhibition LED=Flashing
RELEASE INHIBITED
WAITING FOR RESET
SIGNAL SILENCE?
PREALARM LED= ON
PREALARM RELAY= OFF
BUZZER= Intermittent sound
SILENCED CONTROL LED= ON
Second alarm
Wait Time
= Expired?
SECOND ALARM
ALARM LED= FLASHING
ALARM RELAY= ON
SOUNDER RELAY= ON
EVACUATION RELAY= ON
EVACUATION LED= ON
BUZZER= STEADY SOUNDER
Detector Line Automatic RESET
Prealarm LED= OFF
Prealarm RELAY= OFF
Silenced Control LED= OFF
BUZZER= OFF
WAITING FOR RESET
SIGNAL SILENCE?
ALARM RELAY= OFF
SOUNDER RELAY= OFF
SILENCED CONTROL LED= ON
BUZZER= INTERMITTENT SOUNDER
EVACUATION TIME
= EXPIRED?
Release Actuation
Release LED= ON
PRESSURE-METER ACTIVATED?
RELEASE ACTUATION
RELEASE ACTUATION= 3?
TROUBLE LED= FLASHING
TROUBLE RELAY= ON
BUZZER= INTERMITTENT SOUND
WAITING FOR RESET
EVACUATION 1 LED= ON
RELEASE 1 LED= ON
RELEASE 1 TROUBLE LED= FLASHING
TROUBLE RELAY= ON
TROUBLE LED= ON
BUZZER= INTERMITTENT SOUND
YES
NO
NO
YES
YES
YES
NO
NOTE:ZONE ALARM
Single threshold Zone:
First Alarm= Zone in Alarm status
Double threshold Zone:
First Alarm= Zone in Prealarm status
Second Alarm= Zone in Alarm status
»
NOTE: In “battery trouble” condition
the release never occurs.