CHANGE ZONE PARAMETERS
This section allows to program the following functions, for each zone.
2 THRESHOLDS for each ZONE (this programming allows to detect an alarm coming from 2 different detectors of
the same zone, and use only 1 zone for exstinguishing purposes)
ZONE ALWAYS IN NIGHT MODE (for fire alarm push buttons)
RESET RELAY (this programming enables the resettable voltage output to be activated or not when the zone is in
Walk Test Mode or the zone verification time is enabled).
Press
ENTER
to start the programming
Use
CURSOR
keys and
ENTER
key to select the zone
Press
ENTER
to have access to the Modify menu
Press
ENTER
to modify
CHANGE VERIFICATION TIMES
This section allows to program the alarm verification time for the single zones.
Press
ENTER
Use
CURSOR
Keys to select the zone number on which you wish
to modify the verification time, then press
ENTER
to confirm the
zone number.
Press twice
ENTER
key.
Use
CURSOR
Keys and
ENTER
to set the verification time.
It is possible to program a 999-second maximum time.
Page 12 Installation and Operating Manual CFP-600-Prog-3.VP
NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG
ZONE PARAMETER |A08
CONFIGURATION |G08
|D00
|E00
Z. __ |A08
|G08
|D00
|E00
Z. 01 |A08
2 AL. THRESH. |G08
|D00
|E00
Z. 01 |A08
2 AL. THRESH. |G08
NO |D00
Modify Exit |E00
VERIF. TIME |A08
CONFIGURATION |G08
|D00
|E00
VERIF. TIMES |A08
Z. __ |G08
|D00
|E00
VERIF. TIMES |
Z. 01 |
|
|
VERIF. TIMES |
Z. 01 |
0 __ |
|