HeatWater.com | WaterService@nyle.com | (800) 777-6953 IM-e360-122023 IM-e360-122023 HeatWater.com | WaterService@nyle.com | (800) 777-6953
7
Electrical Specications
Table 2: e360 – Electrical Specications
Electrical Specications Standard Power Package Unied Power Package
Voltage (Volt/Phase/Hz) 208-230/3/60 460/3/60 208-230/3/60
460/3/60
Wire and
Disconnect Sizing
MCA 133 69 140
72
MOCP 222 113 228
116
Running Load Amps (RLA) 110 57 110
57
Power Factor 0.86 0.86
Short Circuit Current Rating (SCCR) 100 100
Internal Component Data
Fan Motor Full Load Amps FLA 10.1 6.0 10.1
6.0
Fan Horsepower (HP) 5.1 6.02 5.1
6.02
Compressor Horsepower (HP) 30 30
Compressor Locked Rotor Amps (LRA) 294 245 294
245
Internal Pump Full Load Amps (FLA) On Back-up Feed 2.1
Backup Circuit Single Phase Power Feed 120/1/60
Min. Circuit Ampacity (MCA) 14 14
Full Load Amps (FLA) 11.3 11.1
Max. Overcurrent Protection (MOCP) 25 20
Internal Pump Full Load Amps (FLA) 2.1 2.1
Circuit Power 1360 1330
Short Circuit Current Rating (SCCR) 100
Note:
Certified to UL 1995 on Certificate LC16035-1
CAUTION
Do not install e-Series heat pumps such that they would
need to be operated in conditions outside of these per-
formance specications. Units may stop compressor
operation outside of ambient temperature limits. In cold
climates, freeze protection measures will remain active
when the compressor is turned off.