EasyManua.ls Logo

Oldham MX 43 - Page 23

Oldham MX 43
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4 The MX 43 Controller
19
Event
Message
screen
Alarm relay
(normal)
Alarm Relay
(buzzer)
LED alarm
Internal
buzzer
Appearance
AL (1,2,3)
and inverse
video of the
detector
Activated
Activated
Fixed light:
Activated
Press alarm
reset
AL (1,2,3)
and inverse
video of the
detector
Activated
Deactivated
Fixed light:
Deactivated
Disappearan
ce
Normal
display
Deactivated
Deactivated
Off:
(a)
(a): Manual release compulsory to stop the internal buzzer.
(b): Automatic deactivation upon alarm disappearance, even if no release has been requested
before the alarm disappearance.
(c): If programmed
Table 2: Automatic deletion of alarms.
Manual deletion of alarms
Release (resetting) by the operator is compulsory. The management of alarms
(relay, indicator, buzzer) is carried out according to the following table:
Event
Message
screen
Alarm relay
(normal)
Alarm relay
(buzzer)
LED alarm
Internal
buzzer
Appearance
AL(1,2,3)
and inverse
video of
detector
Activated
Activated
Blinking light
Activated
Release
activated
AL(1,2,3)
and inverse
video of the
detector
Activated in
the presence
of an event
Deactivated
Fixed light if
an event is
present
Deactivated
AL(1,2,3)
and inverse
video of the
detector
Deactivated
if the event
disappears
Deactivated
Off if an
event
disapears
Disappearan
ce
Normal
display
Deactivated
(1)
Deactivated
Off (1)
Deactivated
(1)
(1): compulsory after manual release.
Table 3: Manual alarm deletion.
Internal relays and buzzers
The operating mode of relays and optional visual and sound alarms (Figure
11, F and G) is configured over the COM 43 application.
Relays: 5 alarm relays (R1 to R5) are common to all the lines.
The internal buzzer is common to all the alarms of all the lines: it is
activated on the appearance of an event (failure or alarm). The common
failure relay is active in parallel. The sound frequency of the internal buzzer
differs in accordance with the alarm threshold. High alarm thresholds have

Related product manuals