66
16-Logic Input Module
Function
Function
Logic input monitoring.
Capacity:
1 to 16 logic inputs (dry contacts).
Connections:
Screwed terminals.
Connector detachable without cutting the line
Tightening torque: 0.5-0.6 Nm.
Cable: 2.5 mm² maximum.
Consumption:
2 mA in normal operation.
Assembly:
Snap-on on DIN rail.
Dimensions:
125 x 165 x 60 mm.
8-Analog Input Module
Function
Function:
4-20mA detector or Wheatstone bridge
connections.
Capacity:
1 to 8 independent inputs.
Connections:
Screwed terminals.
Connector detachable without cutting the line.
Tightening torque: 0.5-0.6 Nm.
Cable: 2.5 mm² maximum.
Consumption:
53 mA max (detector excluded).
Operating temperature:
8 bridges
-30°C (8 bridges up to 1 km).
-40°C (8 bridges up to 500 m).
4 bridges
-45°C (4 bridges up to 1 km).
-50°C (4 bridges up to 500 m).
Assembly:
Snap-on on DIN rail or mounted on the inside of
MX 43.
Dimensions:
125 x 165 x 60 mm.