39
FUNCTION
(Op#).(Fn#) Parameter/Comment
0.26 100% x max output
1.26 95%
2.26 90%
3.26 85%
4.26 80%
5.26 75%
6.26 70%
7.26 65%
8.26 60%
9.26 55%
10.26 50%
11.26 45%
12.26 40%
13.26 30%
14.26 20%
15.26 10%
TABLE 3-6
ADVANCED FUNCTIONS.26 -.50
NOTE
.26 HEATING OUTPUT LIMIT (OUTPUT 1)
These Advanced Functions, .26 through .50,
are not required for day-to-day use. They
should not be accessed except during set-up
by qualified personnel.
Allows adjustment of maximum output to heater in percent.
Example: if 50% (Option 10) is selected, then the output of the
controller would never be allowed to be greater than 50%. This
might be used with an oversized heater. Autotune can not be used
with SP1 heat limit other than 100% (Option 0). Example: with 10
second cycle time 50% (Option 10) would never allow more than 5
sec on 5 sec off when controller calls for 100% output. Not
applicable if SP1 is ON/OFF.