40
Allows reversal of action of SP1 LED (e.g. change to on when
logically off and off when logically on).
TABLE 3-6 (Cont'd)
FUNCTION
.27 COOLING OUTPUT LIMIT (OUTPUT 2)
.28 OUTPUT 1 DIRECT/REVERSE (HEAT/COOL)
.29 OUTPUT 1 LED OPERATION
Same as Function .26 but for cooling. Used when cooler is
oversized. Sets the limit to the maximum cooling power %
required.
(Op#).(Fn#) Parameter/Comment
0.27 100% x max
1.27 80% output
2.27 60%
3.27 50%
4.27 40%
5.27 30%
6.27 20%
7.27 10%
(Op#).(Fn#) Parameter/Comment
0.28 Reverse Acting (Heating)
1.28 Direct Acting (Cooling)
(Op#).(Fn#) Parameter/Comment
0.29 ON when logically on (standard)
1.29 OFF when logically on (reversed)
Allows action of output to set to reverse acting for heating
(standard) or direct acting.
WARNING
Inverting output may affect controller
failsafe characteristics.
Selection should only be made by qualified personnel. Consult
OMEGA if you are not sure of your application. This function is not
available with Software Version 3. Refer to Function .23.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omega C9000A SERIES and is the answer not in the manual?

Omega C9000A SERIES Specifications

General IconGeneral
BrandOmega
ModelC9000A SERIES
CategoryTemperature Controller
LanguageEnglish

Related product manuals