32 OMICRON
Figure 8-8: Step and touch (using HGT1) Excel template (with the EN 50522 tab active)
Maximum Fault Duration:
Additionally considered resistance:
Permissible Touch Voltage:
Required Input Impedance during measurement:
Reduction Factor of Test Current:
Frequency of Test Current:
Amplitude of Test Current at corresponding Frequency:
Maximum Current to Earth:
LocationID
Impedance
Selection
Touch Voltage
HGT1 Results / V
Calculated
/ V
Assessment
300 ms
ȍ
416 V
1 k
1,00
30,0 Hz
70,0 Hz
30 A 30 A
10000 A
fence@gate
transformer
VT1housing
MyLocation
fence@trafo
entryFence
trafo2
VT2housing
CT2housing
CT1housing
1 k
1 k
1 k
1 k
1 k
1 k
1 k
1 k
1 k
1 k
0,00581V
0,00276V
0,00421V
0,00298V
0,00669V
0,00341V
0,00232V
0,00815V
0,00115V
0,00298V
1,68V
1,18V
1,72V
1,01V
1,67V
1,21V
1,22V
2,31V
1,15V
1,01V
0,00430V
0,00432V
0,00613V
0,00311V
0,00337V
0,00385V
0,00500V
0,00577V
0,00577V
0,00311V
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
30,0 Hz 70,0 Hz
1
2
3
4
5
6
7
8
9
10