MX2 Quick Start Guide 13
INSTALLATION
2.8 Digital inputs SINK/SOURCE (NPN/PNP) settings
2.9 Safe stop disable function
MX2 inverter incorporates a SAFE STOP function at hardware level according with EN60204-1 stop category 0. It is designed to
meet the requirements of the ISO13849-1, PL=d and IEC61508 SIL 2 only in a system in which EDM signal is monitored by an
external device monitor. Two redundant inputs are required (3/GS1 and 4/GS2). The function is purely hardware based. but to
activate it you should set below switches to ON. This will fix the configuration of multi-function inputs 3 (C003=77) and 4
(C004=78) and also for the multi-function output 11 (C021=62).
When the switches are set to OFF the multi-function input and output the configuration is set to No function selection
Sinking internal supply
(for NPN outputs)
Sinking external supply
(for NPN outputs
Sourcing internal supply
(for PNP outputs)
Sourcing external supply
(for PNP outputs
P24+V
PLC
L
1
7
24 V DC
Inverter
Short-circuit
bar
COM
Output unit etc.
P24+V
PLC
1
7
24 V DC
Inverter
COM
DC24V
Output unit etc.
L
P24
PLC
1
7
0V
Output unit etc.
24 V DC
Inverter
Short-circuit
bar
COM
L
P24
PLC
1
7
0V
Output unit etc.
24 V DC
Inverter
COM
24 V DC
L