MX2 Quick Start Guide
24 MX2 Quick Start Guide
3.11 Analog inputs
MX2 provides two analog inputs, the input terminal group includes the [L], [OI],
[O], and [H] terminals on the control connector, which provide for Voltage [O] or
Current [OI] input. All analog input signals must use the analog ground [L].
If you use either the voltage or current analog input, you must select one of them
using the logic input terminal function [AT] analog type. Refer to next table for
details about the combinations between A005 and [AT] terminal. Remember that
you must also set A001=01 to select analog input as the frequency source.
If [AT] function is not assigned to any digital input the inverter recognizes the
[AT] as OFF and [O]+[OI] will be used as analog input. In case either (O) or (OI)
is to be referred, please ground the other.
For [O] input and using parameters A013 and A014 you could select the portion of
the voltage input range. Parameters A011 and A012 select the start and end fre-
quency of the converted output frequency range, respectively. When the line does
not begin at the origin (A011 and A013 > 0), then A015 defines whether the
inverter outputs 0 Hz or the A011 specified frequency for analog input below A013.
A005 [AT] Input Analog Input Configuration
00 ON [O]
OFF [OI]
02 ON [O]
OFF Integrated POT on external panel
03 ON [OI]
OFF Integrated POT on external panel
Parameter Parameter name Description
A011 [O] start frequency 0.00 to 400.00
A012 [O] end frequency 0.00 to 400.00
A013 [O] start voltage 0. to 100%
A014 [O] end voltage 0. to 100%
A015 [O] start frequency enable 00... Use offset (A011 value)
01.. Use 0Hz
A101 [OI] start frequency 0.00 to 400.00
A102 [OI] end frequency 0.00 to 400.00
A103 [OI] start voltage 0. to 100%
A104 [OI] end voltage 0. to 100%
A105 [OI] start frequency enable 00... Use offset (A101 value)
01.. Use 0Hz
A016 Analog input filter Range n = 1 to 31,
1 to 30 : ×2ms filter
31: 500ms fixed filter with ±0.1kHz hys.
AM H O OI L
+V Ref.
Voltage input
Current input
A
GND
AM H O OI L
Freq.
setting
V/I input select
[AT]
4-20 mA
0-10 V

1 to 2kΩ, 2 W
Max frequency
A012
A102
A011
A101
A014
A104
100%
0V
10V
A013
A103
0%
A015=
A105=00
00
0
Input scale
%
A015=01
A105=01
I129E-EN-02+MX2+QuickStartGuide.book Seite 24 Mittwoch, 7. November 2012 1:54 13