MX2 Quick Start Guide
36 MX2 Quick Start Guide
4.2 Parameter group A
d010 Torque bias monitor -200 to +200 1 [%] 100Eh
d012 Torque monitor -200 to +200 1 [%] 1010h
d013 Output voltage monitor 0 to 6000 0.1 [V] 1011h
d014 Power monitor 0 to 1000 0.1 [kW] 1012h
d015 (32-bits) Watt-hour monitor 0 to 9999000 0.1 1013h
1014h
d016 (32-bits) Elapsed RUN time monitor 0 to 999900 1 [h] 1015h
1016h
d017 (32-bits) Elapsed power-on time monitor 0 to 999900 1 [h] 1017h
1018h
d018 Heat sink temperature monitor -200 to 1500 0.1 [?] 1019h
d022 Life-check monitor 2^0: Capacitor on main circuit board
2^1: cooling-fan
1 bit 101Dh
d023 Drive programming program counter 0~1024 101Eh
d024 Drive programming program number 0~9999 101Fh
d025(32-bits) User monitor 1 -2147483647 to 2147483647 1 102Eh
102Fh
d026(32-bits) User monitor 2 -2147483647 to 2147483647 1 1030h
1031h
d027(32-bits) User monitor 3 -2147483647 to 2147483647 1 1032h
1033h
d029(32-bits) Position setting monitor -268435455 to 268435455 1 1036h
1037h
d030(32-bits) Position feedback monitor -268435455 to 268435455 1 1038h
1039h
d60 Inverter mode monitor 0 (IM CT)
2(IM High Freq mode)
1(IM VT)
1057h
d80 Trip counter 0 to 65530 - 0011h
d081 Trip info 1 Trip factor
Inverter status
Output frequency (32-bit)
Output current
Output voltage
Running time (32-bit)
Power-on time (32-bit)
- 0012h to
001Bh
d082 Trip info 2 - 001Ch to
0025h
d083 Trip info 3 - 0026h to
002Fh
d084 Trip info 4 - 0030h to
0039h
d085 Trip info 5 - 003Ah to
0043h
d086 Trip info 6 - 0044h to
004Ch
d090 Warning monitor Warning code - 004Eh
d102 DC voltage monitoring (across P and N) 0 to 10000 0.1 [V] 1026h
d103 BRD load factor monitoring 0 to 1000 0.1 [%] 1027h
d104 Electronic thermal overload monitoring 0 to 1000 0.1 [%] 1028h
Function code Function name Monitoring and setting items Units Run
mode
edit
Modbus
Register
Nº
Default
A001 Frequency source 0 (keypad potentiometer), 1 (control circuit terminal
block), 2 (digital operator), 3 (Modbus), 4 (option ), 6
(pulse train input), 7 (easy sequence), 10 (operation
function result)
–  1201h 01
A002 Run command source (*) 1 (control circuit terminal block), 2 (digital operator), 3
(Modbus), 4 (option)
–  1202h 01
A003 Base frequency 300 to "maximum frequency" 0.1 [Hz]  1203h 50.0
A004 Maximum frequency 300 to 4000 (10000) 0.1 [Hz]  1204h 50.0
A005 [AT] selection 0 (switching between O and OI terminals), 2 (switching
between O terminal and keypad potentiometer), 3
(switching between OI terminal and keypad potentiom-
eter)
–  1205h 00
A011 (32-bits) [O] input active range start frequency 0 to 40000(100000) 0.01 [Hz]  120Bh 0.00
120Ch
A012 (32-bits) [O] input active range end frequency 0 to 40000(100000) 0.01 [Hz]  120Dh 0.00
120Eh
A013 [O] input active range start voltage 0 to "[O]-[L] input active range end voltage" 1 [%]  120Fh 0
A014 [O] input active range end voltage "[O]-[L] input active range start voltage" to 100 1 [%] 
1210h 100
A015 [O] input start frequency select 00 (external start frequency), 01 (0 Hz) –  1211h 01
A016 Analog input filter. 1 to 30 or 31 (500 ms filter ±0.1 Hz
with hysteresis)
1  1212h 8
A017 EzSQ selection 00 (disabling), 01 (PRG terminal) , 02 (Always) –  1213h 00
A019 Multi speed operation selection 00 (binary), 01 (bit) –  1215h 00
A020 (32-bits) Multi-speed freq. 0 0 or "start frequency" to "maximum frequency" 0.01 [Hz]  1216h 6.00
1217h
A021 (32-bits) Multi-speed freq. 1 0 or "start frequency" to "maximum frequency" 0.01 [Hz]  1218h 0.00
1219h
Function code Function name Monitoring and setting items Units Modbus
Register No.
I129E-EN-02+MX2+QuickStartGuide.book Seite 36 Mittwoch, 7. November 2012 1:54 13