MX2 Quick Start Guide
6 MX2 Quick Start Guide
2 INSTALLATION
2.1 Wiring sizes and protection
2.2 External dimensions for installation (IP20 & IP54)
Vo lta ge
Inverter rating
(KW)
Inverter Model
Wi ri ng Applicable equipment
VT CT
Power Lines (mm
2
)
Te rm i na l
screw
Tighttening
Toque (N/m)
Signal Lines
Fuse
(UL-rated, class J, 600 V)
1x200V
0.2 0.1 3G3MX2-AB001
AWG16 / 1.3 mm² M4 1.0
18 to 28 AWG
0.14 to 0.75 mm²
shielded wire
10 A0.4 0.2 3G3MX2-AB002
0.55 0.4 3G3MX2-AB004
1.1 0.75 3G3MX2-AB007 AWG12 / 3.3 mm² M4 1.4 15 A
2.2 1.5 3G3MX2-AB015
AWG10 / 5.3 mm² M4 1.4
20 A
3.0 2.2 3G3MX2-AB022 30 A
3x200V
0.2 0.1 3G3MX2-A2001
AWG16 / 1.3 mm² M4 1.0
10 A0.4 0.2 3G3MX2-A2002
0.75 0.4 3G3MX2-A2004
1.1 0.75 3G3MX2-A2007
15 A
2.2 1.5 3G3MX2-A2015 AWG14 / 2.1 mm² M4 1.4
3.0 2.2 3G3MX2-A2022 AWG12 / 3.3 mm² M4 1.4 20 A
5.5 3.7 3G3MX2-A2037 AWG10 / 5.3 mm² M4 1.4
30 A
7.5 5.5 3G3MX2-A2055
AWG6 / 13 mm² M5 3.0
11 7.5 3G3MX2-A2075 40 A
15 11 3G3MX2-A2110 AWG4 / 21 mm² M6 3.9 to 5.1 60 A
18.5 15 3G3MX2-A2150 AWG2 / 34 mm² M8 5.9 to 8.8 80 A
3x400V
0.75 0.4 3G3MX2-A4004
AWG16 / 1.3 mm² M4 1.4
10 A
1.5 0.75 3G3MX2-A4007
2.2 1.5 3G3MX2-A4015
3.0 2.2 3G3MX2-A4022
AWG14 / 2.1 mm² M4 1.4
4.0 3.0 3G3MX2-A4030
15 A5.5 4.0 3G3MX2-A4040 AWG12 / 3.3 mm² M4 1.4
7.5 5.5 3G3MX2-A4055
AWG10/ 5.3 mm² M5 3.0
11 7.5 3G3MX2-A4075 20 A
15 11 3G3MX2-A4110
AWG6 / 13 mm² M6 3.9 to 5.1
30 A
18.5 15 3G3MX2-A4150 40 A
Power Type W (mm) H (mm) D (mm) D1 (mm)
1x 200V
3G3MX2-AB001
3G3MX2-AB002
68 128
109 13.5
3G3MX2-AB004 122.5 27
3x 200 V
3G3MX2-A2001
3G3MX2-A2002
109 13.5
3G3MX2-A2004 122.5 27
3G3MX2-A2007 145.5 50
8.8.8.8.
68
56
Ø4.5
128
118
5
D
D1
2.6
Power Type W(mm) H (mm) D (mm) D1(mm)
1x 200 V
3G3MX2-AB007
108 128
170.5 55
3G3MX2-AB015
3G3MX2-AB022
3x 200 V
3G3MX2-A2015
3G3MX2-A2022
170.5 55
3x 400V
3G3MX2-A4004 143.5 28
3G3MX2-A4007
3G3MX2-A4015
3G3MX2-A4022
3G3MX2-A4030
170.5 55
8.8.8.8.
108
96
128
118
5
D
D1
4.4
2-Ø4.5
I129E-EN-02+MX2+QuickStartGuide.book Seite 6 Mittwoch, 7. November 2012 1:54 13