MX2 Quick Start  Guide 41
PARAMETER LIST
4.4 Parameter group C
Function code Function name Monitoring and setting items Units Run  
mode 
edit
Modbus
Register 
No.
Default
C001 Input [1] function Check  I/O optiosn on page  –  1401h 00 (FW)
C002 Input [2] function –  1402h 01 (RV)
C003 Input [3] function –  1403h 12 (EXT)
C004 Input [4] function –  1404h 18 (RS)
C005 Input [5] function –  1405h 02 (CF1)
C006 Input [6] function –  1406h 03 (CF2)
C007 Input [7] function –  1407h 06 (JG)
C011 Input [1] active state 0 (NO), 1 (NC) –  140Bh 00
C012 Input [2] active state 0 (NO), 1 (NC) –  140Ch 00
C013 Input [3] active state 0 (NO), 1 (NC) –  140Dh 00
C014 Input [4] active state 0 (NO), 1 (NC) –  140Eh 00
C015 Input [5] active state 0 (NO), 1 (NC) –  140Fh 00
C016 Input [6] active state 0 (NO), 1 (NC) –  1410h 00
C017 Input [7] active state 0 (NO), 1 (NC) –  1411h 00
C021 Output [11] function Check I/O options on page –  1415h 00(RUN)
C022 Output [12] function –  1416h 01(FA1)
C026 Alarm relay function –  141Ah 05 (AL)
C027 [EO] terminal selection Check analog and pulse output on page  –  141Bh 07(LAD)
C028 [AM] terminal selection Check analog and pulse output on page  –  141Ch 07(LAD)
C030 Digital current monitor reference value 200 to 2000 0.1 [%] 141Eh -
C031 Output [11] active state 0 (NO), 1 (NC) –  141Fh 00
C032 Output [12] active state 0 (NO), 1 (NC) –  1420h 00
C036 Alarm relay active state 0 (NO), 1 (NC) –  1424h 01
C038 Output mode of low current detection 0 (output during acceleration/deceleration and con-
stant-speed operation), 1 (output only during constant-
speed operation)
–  1426h 01
C039 Low current detection level 0 to 2000 0.1 [%]  1427h -
C040 Overload signal output mode 00 (output during acceleration/deceleration and con-
stant-speed operation), 01 (output only during con-
stant-speed operation)
–
 1428h 01
C041 Overload warning level 0 to 2000 0.1 [%]  1429h -
C042 (high) Frequency arrival setting for accel. 0 to 40000 0.01 [Hz]  142Ah 0.00
C042 (low) 142Bh
C043 (high) Frequency arrival setting for decel. 0 to 40000 0.01 [Hz]  142Ch 0.00
C043 (low) 142Dh
C044 PID deviation level 0 to 1000 0.1 [%]  142Eh 3.0
C045 (high) Frequency arrival setting 2 for accel. 0 to 40000 0.01 [Hz]  142Fh 0.00
C045 (low) 1430h
C046 (high) Frequency arrival setting 2 for decel. 0 to 40000 0.01 [Hz]  1431h 0.00
C046 (low) 1432h
C047 Pulse train input scale conversion for EO output 0.01 - 99.99 –  1433h 1.00
C052 Maximum PID feedback data 0 to 1000 0.1 [%]  1438h 100.0
C053 Minimum PID feedback data 0 to 1000 0.1 [%]  1439h 0.0
C054 Over-torque/under-torqueselection 00(Over torque)/01(under torque) –  143Ah 00
C055 Over-torque (forward-driving) level setting 0 to 200 1 [%]  143Bh 100
C056 Over-torque (reverse regenerating) level setting 0 to 200 1 [%]  143Ch 100
C057 Over-torque (reverse driving) level setting 0 to 200 1 [%]  143Dh 100
C058 Over-torque (forward regenerating) level setting 0 to 200 1 [%]  143Eh 100
C059 Signal output mode of Over/under torque 00 (output during acceleration/deceleration and con-
stant-speed operation), 01 (output only during con-
stant-speed operation)
–  143Fh 01
C061 Electronic thermal warning level 0 to 100 1 [%]  1441h 90
C063 Zero speed detection level 0 to 10000 0.01 [Hz]  1443h 0.00
C064 Heat sink overheat warning level 0 to 110 1 [?]  1444h 100
C071 Communication speed 03(2400bps), 04(4800bps), 05(9600bps), 06(19.2kbps), 
07(38.4kbps),08(57.6kbps), 09(76.8kbps), 
10(115.2kbps)
 –  144Bh 05
C072 Modbus address 1. to 247. –  144Ch 1
C074 Communication parity 00 (no parity), 01 (even parity),
02 (odd parity)
–  144Eh 00
C075 Communication stop bit 1 (1 bit), 2 (2 bits) –  144Fh 01
C076 Selection of the operation after communication 
error
00 (tripping), 01 (tripping after decelerating and stop-
ping the motor), 02 (ignoring errors), 03 (stopping the 
motor after free-running), 4 (decelerating and stopping 
the motor)
–  1450h 02
C077 Communication timeout limit 0 to 9999 0.01 [sec.]
 1451h 0.00
C078 Communication wait time 0 to 1000 1 [msec.]  1452h 0
C081 [O] input span calibration 0 to 2000 0.1  1455h 100.0
C082 [OI] input span calibration 0 to 2000 0.1  1456h 100.0
C085 Thermistor input tuning 0 to 2000 0.1  1459h 100.0
C091 Debug mode enable 00/01 –  145Fh 00
C096 Communication selection 00 (Modbus-RTU) 01(EzCOM)
02 (EzCOM<administrator>)
 1464h 00
C098 EzCOM start adr. of master 1~8  1466h 1
C099 EzCOM end adr. of master 1~8   1467h 1
C100 EzCOM starting trigger 00(Input terminal), 01(Always)  1468h 00
C101 Up/Down memory mode selection 00 (not storing the frequency data), 01 (storing the fre-
quency data)
–  1469h 00
I129E-EN-02+MX2+QuickStartGuide.book  Seite 41  Mittwoch, 7. November 2012  1:54 13