MX2 Quick Start Guide 39
PARAMETER LIST
4.3 Parameter group B
Function code Function name Monitoring and setting items Units Run
mode
edit
Modbus
Register
No.
Default
b001 Restart mode on power failure/ under-voltage trip 00 (tripping), 01 (starting with 0 Hz), 02 (start-
ing with matching frequency), 03 (tripping after decel-
eration and stopping with matching frequency),
04 (restarting with active matching frequency)
–  1301h 00
b002 Allowable under-voltage power failure time 3 to 250 0.1 [sec.]  1302h 1.0
b003 Retry wait time before motor restart 3 to 1000 0.1 [sec.]  1303h 1.0
b004 Instantaneous power failure/under-voltage trip
alarm enable
00 (disabling), 01 (enabling), 02 (disabling during stop-
ping and decelerating to stop)
–  1304h 00
b005 Number of restarts on power failure/under-voltage
trip events
0 (16 times), 1 (unlimited) –  1305h 00
b007 (32-bits) Restart frequency threshold 0 to 40000 0.01 [Hz]  1307h 0.00
1308h
b008 Restart mode on over voltage / over current 00 (tripping), 01 (starting with 0 Hz), 02 (start-
ing with matching frequency), 03 (tripping after decel-
eration and stopping with matching frequency),
04 (restarting with active matching frequency)
–  1309h 00
b010 Number of retry on over voltage / over current 1 to 3 1 [time]  130Bh 3
b011 Retry wait time on over voltage / over current 3 to 1000 0.1 [sec.]  130Ch 1.0
b012 Level of electronic thermal 200 to 1000 0.1 [%]  130Dh -
b013 Electronic thermal characteristic 00 (reduced-torque characteristic),01 (constant-torque
characteristic), 02 (free setting)
–  130Eh 01
b015 Free setting, electronic thermal frequency (1) 0 to 400 1 [Hz]  1310h 0
b016 Free setting, electronic thermal current (1) 0 to Rated current 0.1 [A]  1311h 0.00
b017 Free setting, electronic thermal frequency (2) 0 to 400 1 [Hz]  1312h 0
b018 Free setting, electronic thermal current (2) 0 to Rated current 0.1 [A]  1313h 0.00
b019 Free setting, electronic thermal frequency (3) 0 to 400 1 [Hz]  1314h 0
b020 Free setting, electronic thermal current (3) 0 to Rated current 0.1 [A]  1315h 0.00
b021 Overload restriction operation mode 00 (disabling), 01 (enabling during acceleration and
constant-speed operation),02 (enabling during con-
stant-speed operation), 03 (enabling during accelera-
tion and constant-speed operation [speed increase at
regeneration])
–  1316h 01
b022 Overload restriction level 200 to 2000 0.1 [%]  1317h -
b023 Deceleration rate at overload restriction 1 to 30000 0.1 [sec.]  1318h 1.0
b024 Overload restriction operation mode (2) 00 (disabling), 01 (enabling during acceleration and
constant-speed operation), 02 (enabling during con-
stant-speed operation), 03 (enabling during accelera-
tion and constant-speed operation [speed increase at
regeneration])
–  1319h 01
b025 Overload restriction level 2 200 to 2000 0.1 [%]  131Ah -
b026 Deceleration rate at overload restriction (2) 1 to 30000 0.1 [sec.]  131Bh 1.0
b027 Overcurrent suppression enable 00 (disabling), 01 (enabling) –  131Ch 00
b028 Current level of active freq. matching 100 to 2000 0.1 [%]  131Dh -
b029 Deceleration rate of active freq. matching 1 to 30000 0.1 [sec.]  131Eh 0.5
b030 Start freq. of active frequency matching 00 (frequency at the last shutoff), 01 (maximum fre-
quency), 02 (set frequency)
–  131Fh 00
b031 Software lock mode selection 00 (disabling change of data other than "b031" when
SFT is on), 01 (disabling change of data other than
"b031" and frequency settings when SFT is on), 02 (dis-
abling change of data other than "b031"), 03 (disabling
change of data other than "b031" and frequency set-
tings), 10 (enabling data changes during operation)
–  1320h 01
b033 Motor cable length parameter 5 to 20 –  1322h 10
b034 (32-bits) Run/power-on warning time 0 to 65535 1 [10h]  1323h 0
1324h
b035 Rotation direction restriction 00( Enable for both dir)/ 01 (Enable for forward only)/
02 (Enable for reverse only)
–  1325h 00
b036 Reduced voltage start selection 0 (minimum reduced voltage start time) to 255 (maxi-
mum reduced voltage start time)
–  1326h 2
b037 Function code display restriction 00 (full display), 01 (function-specific display), 02 (user
setting), 03 (data comparison display), 04 (basicdis-
play),05(monitor display)
–  1327h 00
b038 Initial display selection 001-060 –  1328h 001
b039 Automatic user parameter registration 00 (disabling), 01 (enabling) –  1329h 00
b040 Torque limit selection 00 (quadrant-specific setting), 01 (switching by termi-
nal), 02 (analog input)
–  132Ah 00
b041 Torque limit 1 (fwd-power in
4-quadrant mode)
0 to 200/255 (no) 1 [%]  132Bh 200
b042 Torque limit 2 (rev/regen. in
4-quadrant mode)
0 to 200/255 (no) 1 [%]  132Ch 200
b043 Torque limit 3 (rev/power in
4-quadrant mode)
0 to 200/255 (no) 1 [%]  132Dh 200
b044 Torque limit 4 (fwd/regen. in
4-quadrant mode)
0 to 200/255 (no) 1 [%]  132Eh 200
b045 Torque limit LADSTOP enable 00 (disabling), 01 (enabling) –  132Fh 00
b046 Reverse Run protection enable 00 (disabling), 01 (enabling) –  1330h 00
b049 Dual Rating Selection 00(CT mode)/01(VT mode) –  1333h 00
b050 Controlled deceleration on power loss 00 (disabling), 01 (enabling), 02 (nonstop operation at
momentary power failure (no restoration)) 03 (nonstop
operation at momentary power failure (restoration to
be done))
–  1334h 00
b051 DC bus voltage trigger level of ctrl. decel. 0 to 10000 0.1 [V]  1335h 220.0
b052 Over-voltage threshold of ctrl. decel. 0 to 10000 0.1 [V]  1336h 360.0
b053 (32-bits) Deceleration time of ctrl. decel. 0.01 to 36000 0.01 [sec.]  1337h 1.00
1338h
I129E-EN-02+MX2+QuickStartGuide.book Seite 39 Mittwoch, 7. November 2012 1:54 13