MX2 Quick Start Guide 27
PROGRAMMING MX2
An input terminal configured for option code 18 ([RS] Reset command) cannot be configured for normally closed operation.
3.13 Digital outputs
Function codes in the following table let you assign different options into logical outputs (terminals [11],[12] and [AL]) on
parameter C021, C022 and C026..
C011 Input [1] active state Select logic conversion, two option codes:
00... normally open [NO]
01... normally closed [NC]
C012 Input [2] active state
C013 Input [3] active state
C014 Input [4] active state
C015 Input [5] active state
C016 Input [6] active state
C017 Input [7] active state
C160 Input [1] response time Sets response time of each input terminal,
set range:
0 (x 2 [ms]) to 200 (x 2 [ms])
C161 Input [2] response time
C162 Input [3] response time
C163 Input [4] response time
C164 Input [5] response time
C165 Input [6] response time
C166 Input [7] response time
d005 Intelligent input
terminal status
Input Function Summary Table
Option
Code
Terminal
Symbol
Function Name Description
00 RUN Run Signal ON When the inverter is in Run Mode
01 FA1 Frequency Arrival Type 1-
Constant Speed
ON When output to motor is at the set frequency
OFF When output to motor is OFF, or in any acceleration or deceleration ramp
02 FA2 Frequency Arrival Type 2-
Over frequency
ON When output to motor is at or above the set freq., even if in accel (C042) or
decel (C043) ramps
OFF When output to motor is OFF, or at a level below the set frequency
03 OL Overload Advance Notice
Signal 1
ON When output current is more than the set threshold (C041) for the overload sig-
nal
04 OD Output Deviation for PID
Control
ON When PID error is more than the set threshold for the deviation signal
05 AL Alarm Signal ON When an alarm signal has occurred and has not been cleared
06 FA3 Frequency Arrival Type 3-
Set frequency
ON When output to motor is at the set frequency, during accel (C042) and decel
(C043).
07 OTQ Over/under Torque Signal ON Estimated motor torque exceeds the specified level
09 UV Undervoltage ON Inverter is in Undervoltage
10 TRQ Torque Limited Signal ON Torque limit function is executing
11 RNT Run Time Expired ON Total running time of the inverter exceeds the specified value
12 ONT Power ON time Expired ON Total power ON time of the inverter exceeds the specified value
13 THM Thermal Warning ON Accumulated thermal count exceeds the C061 set value
19 BRK Brake Release Signal ON Output for brake release
20 BER Brake Error Signal ON Brake error has occurred
21 ZS Zero Hz Speed Signal ON Output frequency falls below the threshold specified in C063
22 DSE Speed Deviation Excessive ON Deviation of speed command and actual speed exceeds the specified value
P027.
23 POK Positioning Completion ON Positioning is completed
24 FA4 Frequency Arrival Type 4-
Over frequency
ON When output to motor is at or above the set freq., even if in accel (C045) or
decel (C046) ramps
25 FA5 Frequency Arrival Type 5-
Set frequency
ON When output to motor is at the set frequency, during accel (C045) and decel
(C046).
26 OL2 Overload Advance Notice
Signal 2
ON When output current is more than the set threshold (C111) for the overload sig-
nal
27 ODc Analog Voltage Input Dis-
connect Detection
ON When the [O] input value < B070 setting (signal loss detected)
28 OIDc Analog Current input Dis-
connect Detection
ON When the [OI] input value < B071 setting (signal loss detected)
Parameter Parameter name Description
ON
OFF
7 654321
Terminal numbers