MX2 Quick Start Guide
26 MX2 Quick Start Guide
All this functions could be assigned to any of the multi-function inputs on parameters C001 to C007, select if the input will be
normally open or normally close and the response time of the input.
40 TL Torque Limit Selection ON Setting of b040 is enabled
OFF Max. torque is limited with 200%
41 TRQ1 Torque limit switch 1 ON Torque limit related parameters of Powering/regen, and FW/RV modes are selected by the
combinations of these inputs.
42 TRQ2 Torque limit switch 2 OFF
44 BOK Brake confirmation ON Brake confirmation signal received
OFF Brake confirmation signal not received
46 LAC LAD cancellation ON Set ramp times are ignored. Inverter output immediately follows the freq. command.
OFF Accel. and/or decel. is according to the set ramp time
47 PCLR Pulse counter clear ON Clear the position deviation data
OFF Maintain the position deviation data
50 ADD ADD frequency enable ON Adds the A145 (add frequency) value to the output frequency
OFF Does not add the A145 value to the output frequency
51 F-TM Force Terminal Mode ON Force inverter to use input terminals for output frequency and Run command sources
OFF Source of output frequency set by A001 and source of Run command set by A002 is used
52 ATR Enable torque command input ON Torque control command input is enabled
OFF Torque control command input is disabled
53 KHC Clear watt-hour data ON Clear watt-hour data
56 MI1 General purpose input (1) ON General purpose input (1) to (7) under Drive programming
57 MI2 General purpose input (2)
58 MI3 General purpose input (3)
59 MI4 General purpose input (4) OFF
60 MI5 General purpose input (5)
61 MI6 General purpose input (6)
62 MI7 General purpose input (7)
65 AHD Analog command hold ON Analog command is held
OFF Analog command is not held
66 CP1 Multistage-position switch (1) ON Multistage position commands are set according to the combination of these switches.
67 CP2 Multistage-position switch (2) OFF
68 CP3 Multistage-position switch (3)
69 ORL Limit signal of homing ON Limit signal of homing is ON
70 ORG Trigger signal of homing ON Starts homing operation
73 SPD Speed/position changeover ON Speed control mode
OFF Position control mode
77 GS1 * GS1 input ON EN60204-1 related signals: Signal input of "Safe torque off" function.
78 GS2 * GS2 input OFF
81 485 Start EzCOM ON Starts EzCOM
OFF No execution
82 PRG Executing Drive programming ON Executing Drive program
OFF No execution
83 HLD Retain output frequency ON Retain the current output frequency
84 ROK Permission of Run command ON Run command permitted
85 EB Rotation direction detection
(C007 only)
ON Forward rotation
OFF Reverse rotation
86 DISP Display limitation ON Only a parameter configured in b038 is shown
OFF All the monitors can be shown
255 no No function ON (input ignored)
Parameter Parameter name Description
C001 Input [1] function Select input terminal [1] function
C002 Input [2] function Select input terminal [2] function
C003 Input [3] function
[GS1 assignable]
Select input terminal [3] function
C004 Input [4] function
[GS2 assignable]
Select input terminal [4] function
C005 Input [5] function
[PTC assignable]
Select input terminal [5] function
C006 Input [6] function Select input terminal [6] function
C007 Input [7] function Select input terminal [7] function
Input Function Summary Table
Option
Code
Terminal
Symbol
Function Name Description