MX2 Quick Start  Guide 37
PARAMETER LIST
A022 (32-bits) Multi-speed freq. 2 0 or "start frequency" to "maximum frequency" 0.01 [Hz]  121Ah 0.00
121Bh
A023 (32-bits) Multi-speed freq. 3 0 or "start frequency" to "maximum frequency" 0.01 [Hz]  121Ch 0.00
121Dh
A024 (32-bits) Multi-speed freq. 4 0 or "start frequency" to "maximum frequency" 0.01 [Hz]  121Eh 0.00
121Fh
A025 (32-bits) Multi-speed freq. 5 0 or "start frequency" to "maximum frequency" 0.01 [Hz]  1220h 0.00
1221h
A026 (32-bits) Multi-speed freq. 6 0 or "start frequency" to "maximum frequency" 0.01 [Hz]  1222h 0.00
1223h
A027 (32-bits) Multi-speed freq. 7 0 or "start frequency" to "maximum frequency" 0.01 [Hz]  1224h 0.00
1225h
A028 (32-bits) Multi-speed freq. 8 0 or "start frequency" to "maximum frequency" 0.01 [Hz]  1226h 0.00
1227h
A029 (32-bits) Multi-speed freq. 9 0 or "start frequency" to "maximum frequency" 0.01 [Hz]  1228h 0.00
1229h
A030 (32-bits) Multi-speed freq. 10 0 or "start frequency" to "maximum frequency" 0.01 [Hz]  122Ah 0.00
122Bh
A031 (32-bits) Multi-speed freq. 11 0 or "start frequency" to "maximum frequency" 0.01 [Hz]  122Ch 0.00
122Dh
A032 (32-bits) Multi-speed freq. 12 0 or "start frequency" to "maximum frequency" 0.01 [Hz]  122Eh 0.00
122Fh
A033 (32-bits) Multi-speed freq. 13 0 or "start frequency" to "maximum frequency" 0.01 [Hz]  1230h 0.00
1231h
A034 (32-bits) Multi-speed freq. 14 0 or "start frequency" to "maximum frequency" 0.01 [Hz]  1232h 0.00
1233h
A035 (32-bits) Multi-speed freq. 15 0 or "start frequency" to "maximum frequency" 0.01 [Hz]  1234h 0.00
1235h
A038 Jog frequency 0.0, "Start frequency" to 999(10000) 0.01 [Hz]  1238h 6.00
A039 Jog stop mode 0 (free-running after jogging stops [disabled during 
operation])
1 (deceleration and stop after jogging stops [disabled 
during operation])
2 (DC braking after jogging stops [disabled during 
operation])
3 (free-running after jogging stops [enabled during 
operation])
4 (deceleration and stop after jogging stops [enabled 
during operation])
5 (DC braking after jogging stops [enabled during 
operation])
-  1239h 04
A041 Torque boost method selection 00 (manual torque boost),
01 (automatic torque boost)
–  123Bh 00
A042 Manual torque boost value 0 to 200 0.1 [%]  123Ch 1.0
A043 Manual torque boost frequency 0 to 500 0.1 [%]  123Dh 5.0
A044 V/F characteristic curve selection, 1st motor 00 (VC), 01 (VP), 02 (free V/f),
03 (sensorless vector control), 
–  123Eh 00
A045 V/f gain 20 to 100 1 [%]  123Fh 100
A046 Voltage compensation gain setting for automatic 
torque boost, 1st motor
0 to 255 1 [%]  1240h 100
A047 Slippage compensation gain setting for automatic 
torque boost, 1st motor
0 to 255 1 [%]  1241h 100
A051 DC braking enable 00 (disabling), 01 (enabling), 
02 (output freq < [A052])
–  1245h 00
A052 DC braking frequency 0 to 6000 0.01 [Hz]  1246h 0.50
A053 DC braking wait time 0 to 50 0.1 [sec.]  1247h 0.0
A054 DC braking force during deceleration 0 to 100 1 [%]  1248h 50
A055 DC braking time for deceleration 0 to 600 0.1 [sec.]  1249h 0.5
A056 DC braking/edge or level detection for [DB] input 00 (edge operation),
01 (level operation)
–  124Ah 01
A057 DC braking force for starting 0 to 100 1 [%]  124Bh 0
A058 DC braking time for starting 0 to 600 0.1 [sec.]  124Ch 0.0
A059 DC braking carrier frequency setting 20 to 150 0.1 [kHz]  124Dh 5.0
A061 (32-bits) Frequency upper limit 0 or "maximum frequency limit" to "maximum fre-
quency"
0.01 [Hz]  124Fh 0.00
1250h
A062 (32-bits) Frequency lower limit 0 or "maximum frequency limit" to "maximum fre-
quency"
0.01 [Hz]  1251h 0.00
1252h
A063 (32-bits) Jump freq. (center) 1 0 to 40000(100000) 0.01 [Hz]  1253h 0.00
1254h
A064 Jump freq. width (hysteresis) 1 0 to 1000(10000) 0.01 [Hz]  1255h 0.50
A065 (32-bits) Jump freq. (center) 2 0 to 40000(100000) 0.01 [Hz]  1256h 0.00
1257h
A066 Jump freq. width (hysteresis) 2 0 to 1000(10000) 0.01 [Hz]  1258h 0.50
A067 (32-bits) Jump freq. (center) 3 0 to 40000(100000) 0.01 [Hz]  1259h 0.00
125Ah
A068 Jump freq. width (hysteresis) 3 0 to 1000(10000) 0.01 [Hz]  125Bh 0.50
A069 (32-bits) Acceleration hold frequency 0 to 40000 0.01 [Hz]  125Ch 0.00
125Dh
A070 Acceleration hold time 0 to 600 0.1 [sec.]  125Eh 0.0
Function code Function name Monitoring and setting items Units Run 
mode 
edit
Modbus
Register 
Nº
Default