EasyManuals Logo

Omron CJ Series User Manual

Omron CJ Series
304 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #251 background imageLoading...
Page #251 background image
7-19
7 Troubleshooting and Maintenance
CJ-series PROFIBUS Master Unit Operation Manual for NJ-series CPU Unit (W509)
7-4 Troubleshooting the Network
7
7-4-3 Troubleshooting I/O Communication
Problem Probable Cause Correction
PROFIBUS Master Unit
is configured, but none of
the slaves are exchang-
ing data.
No power is supplied to the system.
All indicators on the system are OFF.
Verify that power is supplied to the sys-
tem.
A CPU (startup) error occurred.
The ERH indicator is ON, the other indi-
cators are OFF.
The ERR/ALM indicator on the CPU is
ON.
Determine error in the CPU.
Refer to the NJ Series CPU Unit
Hardware User’s Manual (Cat. No. W500)
and NJ-series CPU Unit Software User’s
Manual (Cat No. W501) for more details
on these errors.
The stored configuration contains a
checksum error (storing configuration was
interrupted or failed).
After restarting the Unit, the ERC indi-
cator is ON and the PRM indicator is
OFF.
Unit Status error flag may provide more
information (*_UnitSta, *_ParamStorErr,
*_ParamLoadErr, *_FileRdErr).
Re-download the configuration.
If the problem persists, replace the Unit.
The configuration contains timing errors.
After restarting the Unit, the ERC indi-
cator is ON, and the PRM indicator is
OFF.
Verify that the Bus parameter sets are
correct.
Re-download the configuration.
If the problem persists, replace the Unit.
The PROFIBUS Master Unit is in either
OFFLINE or STOP mode.
The BST indicator is OFF.
The Unit may have been configured to
maintain its current mode (last mode
was OFFLINE, during download).
The BF indicator is ON: A PROFIBUS
interface error has occurred: see Mas-
ter Errors flags (*_MstrBusErr,
*_MstrProtErr, *_MstrAdrErr,
*_MstrHwErr).
Determine the mode of the Unit: Check
the Master Status word
(*_MstrOperateSta, *_MstrStopSta,
*_MstrClearSta, *_MstrOfflineSta). If Unit
is in OFFLINE or STOP mode:
Verify that the master does not use the
same address as another Master Unit
on the network. Otherwise, correct the
Master Unit’s PROFIBUS address.
Verify that all Master Units on the net-
work use the same baud rate setting.
Otherwise, correct the baud rate set-
tings.
Set CLEAR or OPERATE switch in CIO
Word n (see Note).
Change the configuration to set the Unit
OPERATE mode when switching the
CPU to RUN mode (see Master DTM,
Master Setup Tab). Download the con-
figuration, and switch the CPU to RUN
mode.
Network cabling is not correct.
BF indicator is ON.
Master Errors flag may provide more
information (*_MstrBusErr,
*_MstrProtErr, *_MstrAdrErr,
*_MstrHwErr).
Slave Data Exchange Ative Flags show
which slaves have problems.
Verify that the network installation is cor-
rect:
Verify that all slaves are powered up
and functioning correctly.
Verify that all slave devices are cor-
rectly connected to the network.
Verify that any repeaters used are func-
tioning correctly.
Check the cable length versus the
selected baud rate.
Verify that any stubs used are not too
long.
Verify that termination (resistors and
inductors) are properly set and used.

Table of Contents

Other manuals for Omron CJ Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CJ Series and is the answer not in the manual?

Omron CJ Series Specifications

General IconGeneral
BrandOmron
ModelCJ Series
CategoryController
LanguageEnglish

Related product manuals