204
Adjustment Level Section 5-4
This parameter sets the MV to use when the RUN/STOP status changes
from RUN to STOP.
Related Parameters
RUN/STOP (operation level): Page 185
MV at stop and error addition (advanced function setting level): Page 256
This parameter sets the MV to use when an input error occurs.
Related Parameters
MV at stop and error addition (advanced function setting level): Page 256
mv-s MV at Stop
The control must be set to 2-PID
control.
The MV at Stop and Error Addition
parameter must be ON.
Setting range Unit Default
Standard control: 5.0 to 105.0
Heating/cooling control: 105.0 to 105.0
Position-proportional control (close, with the
Direct Setting of Position Proportional MV
parameter ON): 5.0 to 105.0
%0.0
Position-proportional control (floating or
with the Direct Setting of Positional Propor-
tional MV parameter OFF): CLOS, HOLD,
OPEN
None HOLD
Function
Setting
See
See
mv-e MV at PV Error
The control must be set to 2-PID
control.
The MV at Stop and Error Addition
parameter must be ON.
Setting range Unit Default
Standard control: 5.0 to 105.0
Heating/cooling control: 105.0 to 105.0
Position-proportional control (close, with the
Direct Setting of Position Proportional MV
parameter ON): 5.0 to 105.0
%0.0
Position-proportional control (floating or
with the Direct Setting of Positional Propor-
tional MV parameter OFF): CLOS, HOLD,
OPEN
None HOLD
Function
Setting
See
See