321
Appendix
Note (1) Displayed when there is a remote SP input.
(2) If the PV is selected, the remote SP will be output as long as the SP Mode is set to the Remote SP
Mode.
(3) This setting is ignored for position-proportional control models.
(4) This setting is ignored for models with standard or position-proportional control.
(5) Displayed only when there is a potentiometer input for a model with position-proportional control.
Transfer Output
Lower Limit
tr-l See note 6. See note 6. See note 6.
Linear Current Out-
put
o1-t 4-20: 4 to 20 mA
0-20: 0 to 20 mA
4-20, 0-20 4-20 None
Bank Numbers Used ev-b 0 to 2
0 to 3 (Only when four event
inputs are supported)
1None
Event Input Assign-
ment 1
ev-1 None: None
STOP: RUN/STOP
MANU: Auto/Manual
PRST: Program Start (See
note 3.)
DRS: Invert Direct/Reverse
Operation
AT-2: 100% AT Execute/Can-
cel
AT-1: 40% AT Execute/Cancel
WTPT: Setting Change
Enable/Disable
CMWT: Communications
Write Enable/Disable
LAT: Alarm Latch Cancel
none
stop
manu
prst
drs
at-2
at-1
wtpt
cmwt
lat
NONE None
Event Input Assign-
ment 2
ev-2 None: None
STOP: RUN/STOP
MANU: Auto/Manual
PRST: Program Start (See
note 3.)
DRS: Invert Direct/Reverse
Operation
AT-2: 100% AT Execute/Can-
cel
AT-1: 40% AT Execute/Cancel
WTPT: Setting Change
Enable/Disable
CMWT: Communications
Write Enable/Disable
LAT: Alarm Latch Cancel
none
stop
manu
prst
drs
at-2
at-1
wtpt
cmwt
lat
STOP None
Event Input Assign-
ment 3
ev-3 Same as for Event Input
Assignment 1.
none NONE None
Event Input Assign-
ment 4
ev-4 Same as for Event Input
Assignment 1.
none NONE None
Closed/Floating clfl FLOT: Floating
CLOS: Closed
flot,
clos
FLOT None
Motor Calibration calb OFF, ON off,
on
OFF None
Trave l T i me mot 1 to 999 30 s
Extraction of Square
Root Enable
sqr OFF, ON off,
on
OFF None
Move to Advanced
function Setting
Level
amov −1999 to 9,999 0 None
Parameters Characters Setting (monitor) value Display Default Unit Set value

Table of Contents

Other manuals for Omron E5AN-H

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5AN-H and is the answer not in the manual?

Omron E5AN-H Specifications

General IconGeneral
BrandOmron
ModelE5AN-H
CategoryTemperature Controller
LanguageEnglish

Related product manuals