1 - 27
1 Data List
NX-series Data Reference Manual (W525)
1-5 Analog I/O Units
1
1-5-3 Temperature Input Units
Items in the Summary Specifications
Data List
1-5-3 Temperature Input Units
Temperature Input Units (Screwless Clamping Terminal Block, 12
mm Width)
Item Description
Number of points The number of temperature input points provided by the Unit.
Input type The temperature input type of the Unit.
Conversion time The time required to convert temperature input signals of the Unit to temperature data.
Resolution The resolution of the measured values for the Unit. It is defined in °C.
I/O refreshing method The I/O refreshing methods that are used by the Unit.
Only Free-Run refreshing is available.
In the following table, the following abbreviation is used.
Free: Free-Run refreshing
Model
Unit configuration data Summary specifications
NX Unit
power
consump-
tion [W]
Current
consump-
tion from
I/O power
supply
[mA]
I/O
pow
er
sup-
ply
met
hod
Weig
ht
[g]
Widt
h
[mm]
I/O
data
size
[byte
]
Num-
ber of
I/O
entry
map-
pings
Num
ber
of
poin
ts
Input type
Conver-
sion
time
Resolu-
tion
I/O
refreshin
g
method
CPU
Cou-
pler
NX-TS2101 1.25 0.90 No con-
sumption
No
sup-
ply
70 12 4/0 1/0 2
point
s
Thermo-
couple
250 ms 0.1°C
max.
*1
*1. The resolution is 0.2°C max. when the input type is R, S, or W.
Free
NX-TS2102 1.15 0.80 10 ms 0.01°C
max.
NX-TS2104 0.95 8/0 60 ms 0.001°C
max.
NX-TS2201 1.25 0.90 4/0 Resis-
tance ther-
mometer
250 ms 0.1°C
max.
NX-TS2202 1.15 0.75 Resis-
tance ther-
mometer
10 ms 0.01°C
max.
NX-TS2204 0.90 8/0 Resis-
tance ther-
mometer
60 ms 0.001°C
max.