6 - 19
6 Troubleshooting
NX-series NX1P2 CPU Unit Hardware User’s Manual (W578)
6-2 Troubleshooting
6
6-2-3 Error Table
103D0000 hex NX Unit
Restore
Operation
Failed
The restore opera-
tion for an NX Unit
ended in an error.
• There is also another error
related to the NX Bus Function
Module.
• An NX Bus Communications
Error has occurred.
• The backup data cannot be
sent to an NX Unit.
• The Unit configuration in the
backup file does not agree with
the actual Unit configuration.
S page 6-59
10620000 hex NX Unit
Event Log
Save Error
Saving or reading
the NX Unit event
log failed.
Continuing to oper-
ate with this error
may result in no
event log saved at
CPU Unit power
OFF although it has
no effect on the
control function.
• Data in the NX Unit event log
area are invalid.
S page 6-60
44450000 hex NX Bus Sys-
tem Informa-
tion
This event pro-
vides internal infor-
mation from the NX
Bus Function Mod-
ule.
• This event provides internal
information from the NX Bus
Function Module.
S page 6-60
95800000 hex NX Bus
Restart Exe-
cuted
An NX bus restart
was executed.
• An NX bus restart command
was received.
S page 6-61
Event code Event name Meaning Assumed cause
Level
Reference
Maj Prt Min Obs Info