6 - 19
6 Troubleshooting
NX-series NX1P2 CPU Unit Hardware Users Manual (W578)
6-2 Troubleshooting
6
6-2-3 Error Table
103D0000 hex NX Unit
Restore
Operation
Failed
The restore opera-
tion for an NX Unit
ended in an error.
There is also another error
related to the NX Bus Function
Module.
An NX Bus Communications
Error has occurred.
The backup data cannot be
sent to an NX Unit.
The Unit configuration in the
backup file does not agree with
the actual Unit configuration.
S page 6-59
10620000 hex NX Unit
Event Log
Save Error
Saving or reading
the NX Unit event
log failed.
Continuing to oper-
ate with this error
may result in no
event log saved at
CPU Unit power
OFF although it has
no effect on the
control function.
Data in the NX Unit event log
area are invalid.
S page 6-60
44450000 hex NX Bus Sys-
tem Informa-
tion
This event pro-
vides internal infor-
mation from the NX
Bus Function Mod-
ule.
This event provides internal
information from the NX Bus
Function Module.
S page 6-60
95800000 hex NX Bus
Restart Exe-
cuted
An NX bus restart
was executed.
An NX bus restart command
was received.
S page 6-61
Event code Event name Meaning Assumed cause
Level
Reference
Maj Prt Min Obs Info