6 Troubleshooting
6 - 24
NX-series NX1P2 CPU Unit Hardware Users Manual (W578)
10340000 hex Error in Exe-
cuting SD
Memory Card
Program
Transfer
The SD Memory
Card program
transfer ended in an
error.
It was not possible to read the
data for SD Memory Card pro-
gram transfers.
The SD Memory Card was
removed during a SD Memory
Card program transfer.
There are no backup files in
such a folder on the SD Mem-
ory Card as specified by the
_Card1PrgTransferCmd.Dir-
Name system-defined variable.
The backup files in such a
folder on the SD Memory Card
as specified by the _Card1Prg-
TransferCmd.DirName system-
defined variable are corrupted.
The SD Memory Card is dam-
aged.
S page 6-71
40110000 hex PLC Function
Processing
Error
A fatal error was
detected in the PLC
Function Module.
An error occurred in the soft-
ware.
S page 6-72
44420000 hex PLC Function
Processing
Error
A fatal error was
detected in the PLC
Function Module.
An error occurred in the soft-
ware.
S page 6-72
40120000 hex PLC Function
Processing
Error
A fatal error was
detected in the PLC
Function Module.
An error occurred in the soft-
ware.
S page 6-73
40130000 hex PLC Function
Processing
Error
A fatal error was
detected in part of
the PLC Function
Module.
An error occurred in the soft-
ware.
S page 6-73
10230000 hex Event Log
Save Error
Saving the event
log failed.
A low battery voltage prevented
retention of memory during a
power interruption. (NJ/NX-
series)
A forced shutdown was per-
formed. (NY-series)
Data in the event log area are
invalid. (NY-series)
Data in the NX Unit event log
area are invalid. (NX1P2 CPU
Unit)
S page 6-74
10260000 hex Trace Set-
ting Transfer
Failure
The power supply
was interrupted
while transferring
the trace settings.
The power supply was inter-
rupted while transferring the
trace settings.
S page 6-74