6 Troubleshooting
6 - 26
NX-series NX1P2 CPU Unit Hardware User’s Manual (W578)
102B0000 hex Restore
Operation
Failed to
Start
An error was
detected in pre-
execution checks
for a restore opera-
tion.
• An SD Memory Card is not
inserted.
• The SD Memory Card type is
not correct.
• The format of the SD Memory
Card is not correct.
• There are no backup files on
the SD Memory Card.
• Either the backup files on the
SD Memory Card are corrupted
or required data is not in the
backup files on the SD Memory
Card.
• The unit version of the CPU
Unit to which to restore the files
is older than the unit version of
the backup files on the SD
Memory Card.
• The model of the CPU Unit to
which to restore the files is not
the same as the model of the
CPU Unit of the backup files on
the SD Memory Card.
• Recovery was executed for the
SD Memory Card.
• The CPU Unit is write-pro-
tected.
• The settings in the restore com-
mand file (RestoreCom-
mand.ini) are not correct.
• A backup operation is in prog-
ress.
• Synchronization, online edit-
ing, or the Clear All Memory
operation is in progress.
• The online connection with the
Sysmac Studio was discon-
nected.
• Reading the data for restoration
failed because the SD Memory
Card is faulty or not formatted
correctly.
• The SD Memory Card is dam-
aged.
• The database connection ser-
vice version of the CPU Unit to
which to restore the files is
older than the database con-
nection service version of the
backup files on the SD Memory
Card.
• The robot version of the CPU
Unit to which to restore the files
is older than the robot version
of the backup files on the SD
Memory Card.
Check the followings for specifi-
cation with system-defined vari-
ables.
• Restore by system-defined vari-
able is set to Do not use in the
Controller Setup.
S page 6-78
Event code Event name Meaning Assumed cause
Level
Reference
Maj Prt Min Obs Info

Table of Contents

Other manuals for Omron NX1P2 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron NX1P2 series and is the answer not in the manual?

Omron NX1P2 series Specifications

General IconGeneral
ModelNX1P2 Series
ManufacturerOmron
TypeController
CPU Units1
Program Capacity5 MB
Data Memory Capacity128 KB
Ethernet Ports1
Serial Ports1
Built-in EtherNet/IP PortYes
Built-in EtherCAT PortYes
Built-in USB PortYes
SD Memory Card SlotYes
USB Port1
Power Supply Voltage24 VDC
Programming LanguageLadder, Structured Text, Function Block Diagram
Communication ProtocolsEtherNet/IP, EtherCAT, Serial (RS-232C)