G5 Series AC Servo Drives With Built-in EtherCAT Communications, Linear Motor Type
A-3 Sysmac Error Status Codes
App
A-3-2 Error Description
Event name Servo Drive Overheat Event code 34E10000 hex
Meaning The temperature of the Servo Drive radiator or power elements exceeded the specified value.
Source EtherCAT Master Function Module Source details Slave Detection
timing
Continuously
Error attributes Level Minor fault Recovery Error reset (after
cycling slave
power)
Log category System
Effects User program Continues. Operation Power drive circuit is OFF for relevant slave.
Indicators EtherNet/IP NET RUN EtherNet/IP NET ERR EtherNet/IP LINK/ACT
--- --- ---
System-defined
variables
Variable Data type Name
None --- ---
Cause and
correction
Assumed cause Remedy Prevention
The ambient temperature of the
Servo Drive exceeded the specified
value.
Improve the ambient temperature and
the cooling conditions of the Servo
Drive.
Check the ambient temperature of the
Servo Drive and set up the necessary
cooling conditions.
Overload Increase the capacities of the Servo
Drive and the motor. Or, increase the
setting of the acceleration/
deceleration time and lighten the
load.
Increase the setting of the
acceleration/deceleration time and
lighten the load as much as possible.
Attached
information
None
Precautions/
Remarks
15 is displayed on the Servo Drive front panel and F015 is given as the AlarmCode (4001 hex)