336
PLC Comparison Charts Appendix A
Instruction Comparison
Item Mne-
monic
CJ Series CS Series C200HX/HG/HE CVM1/CV
Series
CQM1H
Sequence
Input
Instructions
LOAD/AND/OR LD/
AND/
OR
Yes Yes Yes Yes Yes
AND LOAD/OR
LOAD
AND
LD/OR
LD
Yes Yes Yes Yes Yes
NOT NOT Yes Yes Yes Yes No
CONDITION ON UP Yes Yes No Yes (*1) No
CONDITION OFF DOWN Yes Yes No Yes (*1) No
BIT TEST TST/
TSTN
Yes (Bit position
specified in
binary:
0000 to 000F
Hex.)
Yes (Bit position
specified in
binary:
0000 to 000F
Hex.)
Yes (Bit position
specified in
BCD.) (*2)
Yes (Bit position
specified in
BCD.) (*1)
No
Sequence
Output
Instructions
OUTPUT OUT Yes Yes Yes Yes Yes
TR TR Yes Yes Yes Yes Yes
KEEP KEEP Yes Yes Yes Yes Yes
DIFFERENTIATE
UP/DOWN
DIFU/
DIFD
Yes (LD
,
AND
, OR)
(LD
, AND,
OR
)
Yes (LD
,
AND
, OR)
(LD
, AND,
OR
)
Yes (DIFU/
DIFD)
Yes (LD
,
AND
, OR)/
(LD
, AND,
OR
)
Yes (DIFU/
DIFD)
SET and RESET SET/
RSET
Yes Yes Yes Yes Yes
MULTIPLE BIT
SET/RESET
SETA/
RSTA
Yes (Beginning
bit and number
of bits specified
in binary.)
Yes (Beginning
bit and number
of bits specified
in binary.)
No (*1)
(Beginning bit
and number of
bits specified in
BCD.)
No
SINGLE BIT SET/
RESET
SET/
RSTB
CJ1: No
CJ1-H: Yes
CJ1M: Yes
CS1: No
CS1-H: Yes
No No No
SINGLE BIT OUT-
PUT
OUTB CJ1: No
CJ1-H: Yes
CJ1M: Yes
CS1: No
CS1-H: Yes
No No No
Sequence
Control
Instructions
END/NO OPERA-
TION
END/
NOP
Yes Yes Yes Yes Yes
INTERLOCK/
INTERLOCK
CLEAR
IL/ILC Yes Yes Yes Yes Yes
JUMP/JUMP END JMP/
JME
Yes (Jump num-
ber specified in
BCD: 0 to 1023)
Yes (Jump num-
ber specified in
BCD: 0 to 1023)
Yes (Jump num-
ber specified in
BCD: 0 to 99.)
Yes (Jump num-
ber specified in
BCD: 0 to 999.)
Yes (Jump num-
ber specified in
BCD: 0 to 99.)
CONDITIONAL
JUMP
CJP/
CJPN
Yes (Jump num-
ber specified in
BCD: 0 to 1023.)
Yes (Jump num-
ber specified in
BCD: 0 to 1023.)
No Yes (Jump num-
ber specified in
BCD: 0 to 999.)
(*1)
No
MULTIPLE JUMP/
JUMP END
JMP0/
JME0
Yes Yes No No (but PLC
Setup can be set
to enable multi-
ple jumps with
jump number 0)
No
FOR/NEXT
LOOPS
FOR/
NEXT
Yes Yes No No No
BREAK LOOP BREAK Yes Yes No No No

Table of Contents