The total Unit power supply capacity for these two blocks is the power supply capacity that the
CPU Rack requires.
Precautions for Correct Use
Select a Unit power supply with sufficient capacity by considering the inrush current when the
power is turned ON. Sometimes, the Unit power supply may not be turned ON caused by inrush
current when the power is turned ON.
Equation in the Slave Terminal
<Equation>
The equation for the Unit power supply capacity in the Slave T
erminal is as follows.
Unit power supply capacity in the Slave T
erminal = Total power capacity from Unit power supply on each
block
The equation for the Unit power supply capacity on each block in the Slave Terminal is as follows.
Required Unit power supply capacity of each block = ((A) + (B))/(C)
(A): NX Unit power consumption of the Unit that supplies NX Unit power
(B): Total power consumption from the NX Unit power supply that is required by the NX Units that are connected to
the Unit that supplies NX Unit power
(C): NX Unit power supply ef
ficiency of the Unit that supplies NX Unit power
<Block>
The following shows the Unit that supplies NX Unit power and its supplying range. For example,
the Slave Terminal in the following diagram is configured with two blocks: the Communications
Coupler Unit block and the Additional NX Unit Power Supply Unit block.