EasyManua.ls Logo

Omron Sysmac NX-PD1000 - Page 91

Omron Sysmac NX-PD1000
194 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Unit name Function
I/O Power Supply Con-
nection Unit
This NX Unit is used when there are not enough I/O power supply terminals for the
connected external devices that are connected to NX Units such as Digital I/O Units
and Analog I/O Units.
I/O power
supply
DC Input Units
(NPN type)
Two-wire sensor*
(e.g., limit switch)
Communications
Coupler Unit
NX Unit
Three-wire sensor
with NPN output*
(e.g., photoelectric sensor
or proximity sensor)
Brown (White)
Blue (Black)
Black (White)
Brown (Red)
Blue (Black)
I/O Power Supply
Connection Unit
(16 IOG terminals)
Example of NPN type
Not enough I/O power
supply terminals
I/O Power Supply
Connection Units
IO
V
A1
A8
B1
B8
A1
A8
B1
B8
A1
A8
B1
B8
IOV
IO
V
IOV
IOV
IOV
IOV
IOV
IOV
IOV
IOV
IOV
IOV
IOV
IOV
IOV
IOV
IOG
IOG
IOG
IOG
IOG
IOG
IOG
IOG
IOG
IOG
IOG
IOG
IOG
IOG
IOG
IOG
1
9
7
5
3
13
11
15
0
8
6
4
2
12
10
14
I/O power supply is not separated at
the I/O Power Supply Connection Units.
Additional I/O
Power Supply Unit
Unit power
supply
I/O power
supply
Internal
power
supply
circuit
I/O Power Supply
Connection Unit
(16 IOV terminals)
* Wire colors have been changed according to revisions in the JIS standards for pho-
toelectric and proximity sensors. The colors in parentheses are the wire colors prior to
the revisions.
4 Installation and Wiring
4-19
NX-series System Units User's Manual (W523)
4-3 Wiring the Power Supply to the Slave Terminal
4
4-3-3 Power Supply-related Units and Wiring Methods