EasyManua.ls Logo

Onan MicroLite 4000 Series

Onan MicroLite 4000 Series
158 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7-6
Start Solenoid (K1)
A check can be made by measuring the resistance
of the coil terminals I and S (Figure 7-4). With the
harness leads removed, the coil should read be-
tween 3 and 5 ohms. If an abnormal reading is mea-
sured, replace the Start Solenoid.
If the coil checks good and a problem with the sole-
noid is still suspected, remove the leads from the
side terminal posts. An open circuit should be mea-
sured between the side terminal posts with the coil
de-energized. With 12 VDC applied across the coil
(I and S terminals) the solenoid should be ener-
gized and continuity should be measured between
the side posts.
Control Assembly (A1)
The Control Assembly consists of a printed circuit
board with components and relays that are potted
(encapsulated in a nonconductive material) to pro-
tect them from moisture. It is difficult to isolate indi-
vidual components on the control assembly for test-
ing. Use Section
6. Troubleshooting
to identify pos-
sible problems in the control circuit. If a problem
with the Control Assembly is suspected, use the
control circuit board tester if available, or check the
control outputs with a voltmeter. Figure 7-5 on Page
7-7 shows the Control Assembly and the P1/J1
connectors. Voltages can be checked using a volt-
meter with long test prods.
WARNING
Electrical shock can cause severe
personal injury or death. Do not touch the volt-
meter or any wiring when the genset is operat-
ing. Attach and remove meter leads only when
the genset is stopped.
Tables 7-1 and 7-2 on Page 7-7 list the control out-
puts at the P1/J1 connector plug for each control
mode. Measure control output voltages between
the connector pin listed and ground. Refer to the
correct chart for Spec A and for Spec B models.
Battery B+ voltage must be present at the Control
Assembly J1-10/P1-10 at all times. If battery volt-
age is present at the J1-10/P1-10 connector and the
control outputs are not present, check the J1/P1
connector and the Start/Stop switch (S1). If the con-
nector and switch check good, replace the Control
Assembly with a new Control Assembly and re-
check genset operation.
TERMINAL
POSTS
I
S
START RELAY K1
FIGURE 7-4. SOLENOID CHECK

Table of Contents

Related product manuals