D-100 Dual Network Interface Installation Guide 03/18 - 1015-2 / 35094 Page 19
2.3 ADDITIONAL BACnet
®
OBJECT INFORMATION
BACnet
®
Object Type and Number of Objects Implemented
Device 1
Analog Input 4
Analog Value 7
Binary Value 5
Property Default Value Read-only or Writable Comment
Object Identier Device - 57017 Writable 0-4,194,303
Object Name BTU Meter - 57017 Writable 50 char. Max
Object Type Device Read-only
System Status Operational Read-only
Vendor Name ONICON Incorporated Read-only
Model Name Display Module Read-only
Firmware Rev. v2.08e Read-only
Location - Writable 36 char. Max
Protocol Version 1 Read-only
Protocol Revision 1 Read-only
Services Supported
Subscribe COV, read Property, read
Property Multiple, write Property
write Property Multiple, device
Communication Control, reinitialize
Device, time Synchronization,
who-Has, who-Is
Read-only
Object Types Supported Analog input, Analog value, Binary
value
Read-only
Object List (Device, 57017), (analog input, 1 – 4),
(analog value, 1 – 13), (binary value,
11 – 15)
Read-only
Max ADPU Length 1458 Read-only
Segmentation Supported NO_SEGMENTATION (3) Read-only
APDU Timeout 10000 Read-only
# of APDU Retries 3 Read-only
Max Master 127 Read-only
Device Address Binding Read-only Active
Database Revision 3 Read-only