1000 SERIES TURBINE METER CONFIGURATION UTILITY AND INSTALLATION GUIDE
ONICON Incorporated 727.447.6140 Page 12 onicon.com
Application Version Number (Read Only)
This is the version number of the ONICON Conguration Utility. This number is
also available in the program window. ONICON may ask for this number if you
are experiencing problems with the utility.
Bootloader Version Number (Read Only)
This is the version number of the ONICON Insertion Turbine Meter rmware. This
number is also available on the window of the program. ONICON may ask for this
number if you are experiencing problems with the utility or turbine meter.
Meter Type (Read Only)
The meter type denes the number of turbines and whether your meter is an
insertion/inline type.
F-1100 – Single Turbine Insertion Flow Meter
F-1200 – Dual Turbine Insertion Flow Meter
F-1101 and F-1134 – Single Turbine Inline Flow Meter
The number of turbines and the body type directly aect the calibration, and
whether the pipe data needs to be entered. For these reasons, the meter type is
set at the factory and is read-only.
Relay Output Conguration (Editable)
The relay output can be congured as:
Not Used – Select this option if you do not want to use the scaled or alarm
output.
Scaled Pulsed Output – Select this option if you want to congure the relay
output as a pulse output for volume totalization
(Example: 1 pulse = 10 gallons).
Alarm Output – Select this option if you want to congure the relay output
as an alarm contact. The relay contact changes state depending on the
alarm status. The alarm status is indicated near the top of the Congurator’s
window, or also viewable on the “Status” tab. An alarm output causes the
relay contact to close. No alarm causes the alarm contact to be open.
Meter Length (Read Only)
The meter length is the distance between the bottom of the meter’s black
electronics enclosure and the end of the meter. This distance is used in the
calculation of the insertion depth in the “Pipe Selection” tab. This length is invalid
when the meter type is set for “F-1101 and F-1134.”
Meter Factor (Read Only)
The meter factor has units of pulses per gallon and is the response characteristic
of the turbine(s). This value is measured when the meter is wet calibrated at
ONICON.