1000 SERIES TURBINE METER CONFIGURATION UTILITY AND INSTALLATION GUIDE
February 2019
• Tampered – Please contact ONICON if this warning is present.
• Watchdog Reset – Please contact ONICON if this warning is present.
• Hard Reset – Please contact ONICON if this warning is present.
• Calibration Not Complete – Please contact ONICON if this warning is
present.
• Commissioning Not Complete – Please contact ONICON if this warning
is present.
• Manufacturing Not Complete – Please contact ONICON if this warning
is present.
• Pulse Overrun – This warning occurs when the scaled pulse output
for totalization is occurring faster than what is allowed, based on the
settings in the “Scaled Pulse Output” tab. To resolve this warning, either
the “Scaled Output Multiplier” needs to be increased, or the “Scaled
Output Pulse Duration” needs to be set to a shorter duration.
3.3.10 FIRMWARE UPDATE
The Firmware Update tab is used just as it is described, to update the
rmware on the insertion turbine meter processor.
This tab should not be used unless you are specically instructed to do so by
ONICON.