F
-
1000 SERIES TURBINE METER CONFIGURATION UTILITY AND INSTALLATION GUIDE
ONICON Incorporated 727.447.6140 Page 21 onicon.com
3.3.5 SCALED PULSE OUTPUT
The scaled pulse output tab provides parameters for conguring the units of
measurement and scaling of the relay output. The relay output is available on all
versions of the Insertion Turbine Meter. The “Relay Output Conguration” in the
“Meter Data” tab must be congured as a “Scaled Pulse Output” for this tab to be
visible.
Scaled Pulse Output tab
Scaled Pulse Output Units (Editable)
This parameter allows the user to set the units of measurement for the scaled
output. This parameter is a duplicate of the parameter with the same name in the
“Flow Settings” tab.
After selecting the units of measurement, press the “Set” button to accept your
changes.
Scaled Output Multiplier (Editable)
This parameter allows the user to set the volume that each pulse is worth. The
available selections are:
1, 10, 100, 1000, or 10000 units of volume per pulse.
Press the “Set” button to accept any changes which are made.
The pulse volume along with the pulse duration determine when the meter
will enter a “pule overrun” alarm. A pulse overrun occurs when the meter is
attempting to provide a scaled pulse faster than the duration allows. Please
follow the on-screen instructions for determining if your pulse scaling and
duration settings could cause a pulse overrun.