F
-
1000 SERIES TURBINE METER CONFIGURATION UTILITY AND INSTALLATION GUIDE
ONICON Incorporated 727.447.6140 Page 17 onicon.com
When inserting the meter into the pipe, push the meter in until the distance from
the pipe wall to the bottom of the meter’s black electronics enclosure matches
the gauge length:
3.3.3 FLOW SETTINGS
The ow settings tab contains conguration parameters which allow the user
to set the ow rate and scaled output units, analog output scale, and meter
damping.
Flow Setting Tab
Full Scale Flow Rate in Volume Rate Units (Editable)
This parameter sets the value for the 20mA/10V/5V analog output full scale, if the
meter has an analog output. The units of measurement will match that set in the
“Volume Rate Units” parameter also on this tab.
After entering the value on this page, press the “Set” button to permanently
program the meter with this output scale.
ONICON recommends that the analog output range is set to 1.25 times larger
than the maximum realistic ow rate which could occur in the system.