F
-
1000 SERIES TURBINE METER CONFIGURATION UTILITY AND INSTALLATION GUIDE
ONICON Incorporated 727.447.6140 Page 27 onicon.com
3.3.8 STATISTICS
The statistics tab provides some of the data already appearing in the “Real-time
Data” tab, and in addition provides historical information about the meter’s
operation.
Statistics tab
Flow Velocity fps (Read Only)
Shows the ow velocity, in feet per second, that the average turbine pulses is
equivalent to based on the pipe ID congured in the “Pipe Selection” tab. This
velocity is corrected for the amount of pipe area the turbine meter acquires
from being inserted in the pipe to the “Gauge Length” position. Therefore, it is
equivalent to the Pipe Velocity fps in the Real-time Data tab.
Total Scaled Pulses (Read Only)
This value shows the number of scaled pulses produced by the meter since
operation.
This value is useful for troubleshooting the scaled output on the meter. If
your BMS is not recording pulses, it should be veried that this value is not
incrementing. If it is incrementing, then the problem lies in the wire connection,
or the conguration of the BMS input. This value can only be reset at the
ONICON factory during recalibration service.
Total Gallons (Read Only)
This value shows the number of gallons measured by the meter since operation.