User Dened Volume Total gallon (Resettable)
This value provides a user-resettable totalizer built-in the turbine ow meter.
By resetting the value to zero, and then verifying the reading after X minutes,
this value can be used as a means to compare the ow meter’s actual volume
measurement over X period of time to a volume measurement acquired through
the use of a BMS connected to the scaled output, or the volume reported by a
local ONICON display or BTU meter.
Run Seconds (Read Only)
This value displays the length of the time the meter has been operational in
seconds.
Run Hours (Read Only)
This value displays the length of time the meter has been operational in hours.
Average Pulses Per Second (Read Only)
This parameter reports the average turbine signal pulses per second (Hz). The
average is the mean of the top and bottom turbine signal pulses per second.
Top Pulses Per Second (Read Only)
This parameter reports the top turbine signal pulses per second (Hz).
If the bottom turbine reports a Hz value, yet the top shows none, the turbine
meter should be inspected for debris or damage.
Bottom Pulses Per Second (Read Only)
This parameter reports the bottom turbine signal pulses per second (Hz).
If the top turbine reports a Hz value, yet the top shows none, the turbine meter
should be inspected for debris or damage.
Total Average Turbine Pulses (Read Only)
This value displays the total number of average turbine pulses measured
since the turbine meter has been operational. The average turbine pulses is
approximately equal to the mathematical mean of the top and bottom turbine
pulse count.
Total Top Turbine Pulses (Read Only)
This value displays the total number of top turbine pulses measured since the
meter has been operational. A top turbine pulse occurs when a blade of the top
turbine passes the top electrode while the meter is submerged in a conductive
medium.