1000 SERIES TURBINE METER CONFIGURATION UTILITY AND INSTALLATION GUIDE
ONICON Incorporated 727.447.6140 Page 14 onicon.com
Pipe Size Programming Method (Editable)
The programming method denes how the pipe information is input by the user.
Two options are available:
Table – The application pipe ID, OD, and remaining stem is automatically
calculated based on the pipe material, size, and schedule selected from the
table on this page.
IMPORTANT
The “SET” button must be pressed after selecting “Table”.
To select a pipe size from the table, open the tree to the specic pipe
material, schedule, and size that your meter will be installed in. Click on that
pipe size, and then press the “Select Standard Pipe” button.
Once you select the pipe size, the ID, OD, remaining stem lengths, and
gauge length will auto-ll with the correct dimensions. The white box above
the “Select Standard Pipe” button will auto-ll with the description of the
selected pipe:
Location of “Set” button
Selecting pipe size and conrming via “Select Standard Pipe” button
#1 Select Pipe
#2 Press Button