4.3 START-UP AND COMMISSIONING WORKSHEET
Please read all installation instructions carefully prior to proceeding with these steps. Use the
following worksheet for checking off the commissioning steps and recording measured values. The
following steps require ow in the pipe. Flow signal readings should be taken while holding the
ow rate constant, if possible. Otherwise, take the various output readings as quickly as possible.
STEP TEST/MEASUREMENT S/N: _________ S/N: ________ S/N: ________ S/N: _________
1. Meter location:
2. Conrm pipe size:
3. Insertion depth and
orientation:
4. Control system
programming:
5. Match display or Btu
meter serial number
(S/N) if ordered:
6. Signal connections
veried:
7. Supply voltage veried:
8. Connect power:
The following steps require ow in the pipe. Flow signal readings should be taken while holding the ow rate
constant if possible, otherwise, take the various output readings as quickly as possible.
9. Frequency output(s):
Avg = green
Average frequency (Hz):
Average frequency
(VDC):
Calculated ow rate:
___________Hz
_________VDC
_________GPM
___________Hz
_________VDC
_________GPM
___________Hz
_________VDC
_________GPM
___________Hz
_________VDC
_________GPM
10. Analog or pulse
output(s)
4-20 mA signal:
0-5 / 0-10 V signal:
Scaled output interval:
Calculated ow rate:
___________mA
_________VDC
_____________
_________GPM
___________mA
_________VDC
_____________
_________GPM
___________mA
_________VDC
_____________
_________GPM
__________mA
_________VDC
_____________
_________GPM
11. Flow rate displayed
by control system:
_________GPM _________GPM _________GPM _________GPM