6.5 Installing the driver
The driver is designed so that heat is dissipated via air convection and
conduction through the enclosure. Install the driver to a at metal plate
oering excellent vibration resistance.
When two or more drivers are installed side by side, provide 20 mm (0.79in.)
and 25 mm (0.98 in.) clearances in the horizontal and vertical directions,
respectively.
20 mm (0.79 in.) or more
Vertical direction
Note
•
Install the driver in an enclosure whose pollution degree is 2 or better environment, or whose degree of
protection is IP54 minimum.
•
Do not cover the radiation vent of the driver.
•
Do not install any equipment that generates a large amount of heat or noise near the driver.
•
If the ambient temperature of the driver exceeds 40°C (104°F), revise the ventilation condition or force-
cool the area around the driver using a fan.
Installing with screws
Install the driver through the driver mounting holes using two screws (M4: not included).
When mounting in vertical direction [Unit: mm (in.)]
147 (5.79)
147 (5.79)
Ø4.5 (Ø0.177) 2ר4.5 (
• When using side surface A • When using side surface B
B
When mounting in horizontal direction [Unit: mm (in.)]
147 (5.79)
147 (5.79)
Ø4.5 (Ø0.177)
• When using side surface A
• When using side surface B
A
B
2ר4.5 (Ø0.177)