H1 (H2) Control circuit → H1 (H2) Setting values → Temperature drop → Temp.drop Exception schedule
H1 (H2) Control circuit → H1 (H2) Setting values → Service setting values
3.3.1.2 Exception schedule
3.3.2 Service setting values
You can easily make changes that dier from normal routine use
by using the holiday schedule. The date, time and mode to which
heating will be changed in the period in question are entered in
the holiday schedule. To switch from an Exception schedule to
weekly schedule mode, select automatic mode.
The access to the Service setting values requires entering the ser-
vice code. The service settings are typically needed only when the
controller is configured and taken in use.
In addition to service settings, there are also other settings for configu-
ration (navigate to ”System settings” → ”Connections and configuration”)
The picture shows an exception
schedule program. Heat reduction
is on from 31 March 2016,
11:30 to 14 April 2016, 16:00
Date Time
Date Time
31.03.2016 11:30 Drop On
14.04.2016 16:00 Automatic
Add new
31.03.2014 11:30 Drop On
Add new
Date Time
Add new
>
Temperature drop by using Exception schedule:
1. Navigate to ”Exception schedule” and press OK. The display will
read ”Add new.” Press OK.
2. Press OK and set the start date for the temperature program, then
the time and “Drop On” mode.
3. Select, if the exception schedule repeats or not. If you select
repeat, it can be repeated every month same time or every year
same time.
4. Accept the holiday schedule you created by pressing ”Ready.
5. Navigate to ”Add new” and press OK.
6. Press OK and set the end date for the temperature drop program,
then the time. Select “Automatic” mode. If you chose earlier (para-
graph 3) “repeat every year” or repeat every month”, select now
same way.
7. Accept the Exception schedule you created by pressing ”Ready.
Temperature drop prevention:
The Exception schedule overrides the Weekly schedule. You can by-
pass the temperature drops for specific time with Exception schedule.
Define the program as above (see steps 1-6), but set the mode to ”Drop
o” in step 2.
1
Date: 31.03.2015
Aika: 11:30
Mode: Drop On
Repeat: No
Accept: Ready
2
3
4
Date: 14.04.2016
Time: 16:00
Mode: Automatic
Repeat: No
Accept: Ready
6
7
5
>
>
>
>
>
NOTE! Remember to also set the end
time for the holiday calendar program!
When you set the date and time, the
mode will change to ”Automatic”. In this
case, the control returns back to the
weekly schedule.
Deleting an activation time from an Exception schedule:
1. Navigate to the row with the activation time you want to delete.
2. Select ”Delete switch time.
3. Accept the deletion by pressing ”Ready.
Setting
Factory
setting
Range Explanation
--- ACTUATOR CONTROL ---
Actuator selection 3-point 3-point,
0(2)-10V,
10 - 0(2) V
3-point or voltage controlled actuators can be used for heating circuits.
Actuator running
time open
150 5...500 s The running time indicates how many seconds go by if the actuator
Actuator running
time close
150 5...500 s runs a valve nonstop from a closed position to an open position