112
Diagnosis
display
Abnormality /
Protection control
Abnormality
Judgment
Protection
Operation
Problem Check location
H41
Abnormal wiring or
piping connection
— —
Wrong wiring and
connecting pipe, expansion
valve abnormality
Check indoor/outdoor
connection wire and connection
pipe
Expansion valve and lead wire
and connector
H59
ECONAVI sensor
abnormality
Continuous for 25s
ECONAVI sensor open or
short circuit
ECONAVI sensor (defective or
disconnected)
ECONAVI PCB
H64
Outdoor high
pressure sensor
abnormality
Continuous for 1
minutes
High pressure sensor open
circuit during compressor
stop
High pressure sensor
Lead wire and connector
H67 Nanoe abnormality
Nanoe stop for 5
minutes for 3 times
— Nanoe faulty
PCB
Nanoe system
High voltage
H70
Light sensor
abnormality
Continuous for 24
hours, 15 days
Light sensor open or short
circuit
Light sensor (defective or
disconnect)
H97
Outdoor fan motor
mechanism lock
2 times happen
within 30 minutes
Outdoor fan motor lock or
feedback abnormal
Outdoor fan motor lead wire
and connector
Fan motor lock or block
H98
Indoor high pressure
protection
— —
Indoor high pressure
protection (Heating)
Check indoor heat exchanger
Air filter dirty
Air circulation short circuit
H99
Indoor operating unit
freeze protection
— —
Indoor freeze protection
(Cooling)
Check indoor heat exchanger
Air filter dirty
Air circulation short circuit
F11
4-way valve
switching
abnormality
4 times happen
within 30 minutes
4-way valve switching
abnormal
4-way valve
Lead wire and connector
F17
Indoor standby units
freezing abnormality
3 times happen
within 40 minutes
Wrong wiring and
connecting pipe, expansion
valve leakage, indoor heat
exchanger sensor open
circuit
Check indoor/outdoor
connection wire and pipe
Indoor heat exchanger sensor
lead wire and connector
Expansion valve lead wire and
connector
F90
Power factor
correction
(PFC) circuit
protection
4 times happen
within 10 minutes
Power factor correction
circuit abnormal
Outdoor PCB faulty
F91
Refrigeration cycle
abnormality
2 times happen
within 20 minutes
Refrigeration cycle
abnormal
Insufficient refrigerant or valve
close
F93
Compressor
abnormal revolution
4 times happen
within 20 minutes
Compressor abnormal
revolution
Power transistor module faulty
or compressor lock
F94
Compressor
discharge overshoot
protection
4 times happen
within 30 minutes
Compressor discharge
pressure overshoot
Check refrigeration system
F95
Outdoor cooling high
pressure protection
4 times happen
within 20 minutes
Cooling high pressure
protection
Check refrigeration system
Outdoor air circuit
F96
Power transistor
module overheating
protection
4 times happen
within 30 minutes
Power transistor module
overheat
PCB faulty
Outdoor air circuit (fan motor)
F97
Compressor
overheating
protection
3 times happen
within 30 minutes
— Compressor overheat
Insufficient refrigerant
F98
Total running current
protection
3 times happen
within 20 minutes
— Total current protection
Check refrigeration system
Power source or compressor
lock
F99
Outdoor direct
current (DC) peak
detection
Continuous
happen for 7 times
Power transistor module
current protection
Power transistor module faulty
or compressor lock

Table of Contents

Other manuals for Panasonic CS-Z25VKEW

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CS-Z25VKEW and is the answer not in the manual?

Panasonic CS-Z25VKEW Specifications

General IconGeneral
AC input voltage230 V
Design load (cooling)2.5 kW
Annual energy consumption (cooling)103 kWh
Hourly energy consumption (cooling)- kWh
Design load (heating) (Warmer heating season)- kW
Design load (heating) (Average heating season)2.7 kW
Energy efficiency class (heating) (Colder heating season)-
Energy efficiency class (heating) (Average heating season)A+++
Annual energy consumption (heating) (Average heating season)741 kWh
TypeAir conditioner indoor unit
Multi-splitNo
Product colorWhite
Dehumidifying capacity1.5 l/h
Air conditioner functionsCooling, Dehumidifying, Heating
Cooling capacity in watts (max)3200 W
Cooling capacity in watts (min)850 W
Heating capacity in watts (max)5000 W
Heating capacity in watts (min)800 W
Cooling capacity in watts (nominal)2500 W
Cooling energy efficiency (EER, W/W)4.81
Heating energy efficiency (COP, W/W)4.79
Seasonal efficiency rating (cooling) (SEER)8.5
Seasonal efficiency rating (heating) (SCOP)5.1
Heating capacity in watts (nominal) (Warmer heating season)- W
Heating capacity in watts (nominal) (Average heating season)3400 W
Indoor unit typeWall-mountable
Indoor unit depth194 mm
Indoor unit width919 mm
Indoor unit height295 mm
Indoor unit weight10000 g
Indoor units quantity1
Cooling airflow (indoor unit)612 m³/h
Heating airflow (indoor unit)672 m³/h
Indoor unit sound power level55 dB
Indoor unit noise level (low speed)19 dB
Indoor unit noise level (high speed)39 dB
Wi-FiYes
Outdoor unit noise level- dB

Related product manuals