15. Operation Control (For Multi Split Connection)
During multi split connection, indoor unit’s operation controls are same with single split connection unless specified in
this chapter.
15.1 Cooling operation
15.1.1 Thermostat control
Capability supply to indoor unit is OFF (Expansion valve closed) when Intake Air Temperature — Internal setting
temperature < -2.0°C.
Capability resume supply to indoor unit after waiting for 3 minutes, if the Intake Air temperature — Internal setting
temperature > Capability supply OFF point.
15.2 Soft Dry Operation
15.2.1 Thermostat control
Capability supply to indoor unit is OFF (Expansion valve closed) when Intake Air Temperature Internal setting
temperature < -3.0°C.
Capability resume to indoor unit after waiting for 3 minutes, if the Intake Air temperature Internal setting
temperature > Capability supply OFF point.
15.3 Heating Operation
15.3.1 Thermostat control
Capability supply to indoor unit is OFF (Expansion valve closed) when Intake Air Temperature Internal setting
temperature > +1.0°C.
During this condition, the indoor fan is stopped if compressor is ON.
Capability resume supply to indoor unit after waiting for 3 minutes, if the Intake Air Temperature Internal
setting temperature < Capability supply OFF point.
15.3.2 Temperature Sampling Control
Temperature sampling is controlled by outdoor unit where room temperature for all power supply ON indoor unit
could be obtained.
When capability supply to the indoor unit is OFF and the compressor is ON, the indoor fan motor is stopped.
During this condition, 15 seconds after sampling signal from outdoor unit is received, the indoor fan start
operation at low fan speed.
However, within first 4 minutes of capability stopped supply to the indoor unit, even sampling signal is received,
the sampling control is cancelled.

Table of Contents

Other manuals for Panasonic CS-Z25VKEW

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CS-Z25VKEW and is the answer not in the manual?

Panasonic CS-Z25VKEW Specifications

General IconGeneral
AC input voltage230 V
Design load (cooling)2.5 kW
Annual energy consumption (cooling)103 kWh
Hourly energy consumption (cooling)- kWh
Design load (heating) (Warmer heating season)- kW
Design load (heating) (Average heating season)2.7 kW
Energy efficiency class (heating) (Colder heating season)-
Energy efficiency class (heating) (Average heating season)A+++
Annual energy consumption (heating) (Average heating season)741 kWh
TypeAir conditioner indoor unit
Multi-splitNo
Product colorWhite
Dehumidifying capacity1.5 l/h
Air conditioner functionsCooling, Dehumidifying, Heating
Cooling capacity in watts (max)3200 W
Cooling capacity in watts (min)850 W
Heating capacity in watts (max)5000 W
Heating capacity in watts (min)800 W
Cooling capacity in watts (nominal)2500 W
Cooling energy efficiency (EER, W/W)4.81
Heating energy efficiency (COP, W/W)4.79
Seasonal efficiency rating (cooling) (SEER)8.5
Seasonal efficiency rating (heating) (SCOP)5.1
Heating capacity in watts (nominal) (Warmer heating season)- W
Heating capacity in watts (nominal) (Average heating season)3400 W
Indoor unit typeWall-mountable
Indoor unit depth194 mm
Indoor unit width919 mm
Indoor unit height295 mm
Indoor unit weight10000 g
Indoor units quantity1
Cooling airflow (indoor unit)612 m³/h
Heating airflow (indoor unit)672 m³/h
Indoor unit sound power level55 dB
Indoor unit noise level (low speed)19 dB
Indoor unit noise level (high speed)39 dB
Wi-FiYes
Outdoor unit noise level- dB

Related product manuals