Because the opto inputs and relay outputs may be assigned to a variety of functions, as detailed
in the following sections, this table can only show the location of the relays and optos.
Common Points
All inputs share a single common. To use the box ground as the common, connect Ground (pin
24) to Opto common (pin 23) on the I/O connector.
All relays share a common point. By default, the relays are configured in a dry contact
configuration. To convert the unit to wet contacts, connect +24 VDC (pin 21) to Relay common
(pin 22) on the I/O connector. This makes all outputs wet contacts; the unit does not support
configurations with some wet and some dry contacts.
Equivalent Circuit