B19
−−
B18
−
English
3. System Conguration and Wiring
Wiring of the Main Circuit
(Terminal block type)
F-frame, 200 V type
•Wiringshouldbeperformedbyaspecialistoranauthorizedpersonnel.
•Donotturnonthepoweruntilthewiringiscompleted.
•Nevertouchtheterminaltowhichhighvoltageisapplied.Thereisariskofelectric
shock.
• Tips on Wiring
1)Takeoffthecoverxingscrews,anddetachtheterminalcover.
2)Makewiring
Useclamptypeterminalsofroundshapewithinsulationcoverforwiringtotheter-
minalblock.Forcablediameterandsize,referto“DriverandListofApplicablePe-
ripheralEquipments”(P.B14).
Tightentheterminalblockscrewwithatorquebetween1.0and1.7N
•
m.
3)Attachtheterminalcover,andxwithscrews.
TightenthescrewsecuringthecoverwithatorquewrittenonP.B15.
Motor
Varistor
DC
24 V
L1
U
V
W
E
L2
L3
L1C
L2C
B1
B3
B2
NC
U
V
W
• Check the name plate of the driver for power
specifications.
• Provide a residual current device. The residual current
device to be the one designed for "Inverter" and is
equipped with countermeasures for harmonics.
• Provide a circuit breaker.
• Make sure to provide a noise filter.
• Provide coil surge suppression units to the coil of the
Magnetic Contactor recommended by manufacturer.
Never start/stop the motor with this Magnetic
Contactor.
• Provide an AC Reactor.
• Don't disconnect the short bar between B1 and B2.
Disconnect this only when an external regenerative
register is used.
• Do not connect anything to NC.
• Match the colors of the motor lead wires to those of the
corresponding motor output terminals (U,V,W).
• Avoid shorting and grounding.
Don't connect the main power.
• Earth-ground this.
• To prevent electric shock, be sure to connect the ground
terminal ( ) of the driver, and the ground terminal
(ground plate) of the control panel.
• The ground terminal ( ) must not be shared with other
equipment.
Two ground terminals are provided.
• Don't connect the earth cable to other inserting slot,
nor make them touch.
• Compose a duplex Brake Control Circuit so that the
brake can also be activated by an external immediate
stop signal.
• The holding Brake has no polarity.
• For the capacity of the holding brake and how to use it,
refer to P.B43, "Specifications of Built-in Holding Brake".
• Provide a varistor.
• Connect a 10 A fuse in series with the varistor.
Ground resistance: 100 Ω max.
For applicable wire, refer to P.B14.
DC power
supply
for brake
Fuse (125 V 10 A)
Red
Black
Green
White
MCCB
Power
supply
NF MC LRCD
External regenerative
resistor
* These colors
are used for
optional cable.
3. System Conguration and Wiring
Wiring method to connector
•
FollowtheproceduresbelowforthewiringconnectiontotheConnector
XA
,
XB
and
XC
.
How to connect
1.Peelofftheinsulationcoverofthecable.
•Forsinglewire(Pleaseobeythelengthingure.)
•Forstrandedwires(ferrulesmustbeusedasillustratedbelow).
Example:
Ferrules with plastic insulating sleeve (AI series, Phoenix Contact, Ltd.)
1)Peeloffthesheathsothattheconductorportionofthecablewillprotrudefrom
thetipoftheferrule.(Itshouldprotrude
1mmormorefromtheferrule.)
2)Insertthecableintotheferruleandcrimp
itwithanappropriatecrimpingtool.
3)Aftercrimping,cutoffthecableconductor
portionprotrudingfrom the ferrule. (The
allowableprotrudinglength aftercutting
shouldbe0to0.5mm.)
•PartNo.ofthecrimpingtool:
CRIMPFOXU-D66(1204436)
AvailablefromPhoenixContact,Ltd.
Examples: Nylon-insulated ferrule (NTUB series, J.S.T. Mfg. Co., Ltd.)
Vinyl-insulated ferrule (VTUB series, J.S.T. Mfg. Co., Ltd.)
1)Peeloffthe sheathofthecableconduc-
tor portiontothelengthequalto that of
sheathontheferrule.
2)Insertthecableintotheferruleandcrimp
itwithanappropriatecrimpingtool.
•PartNo.ofthecrimpingtool:YNT-1614
AvailablefromJ.S.T.Mfg.Co.,Ltd
<Cables Compatible with Connector>
ConductorSize AWG18to12
SheathOutline φ2.1toφ4.2mm
<Recommended Connector Bar Terminal>
ConductorSize AWG18
TerminalModelNumber AI0.75-8GY(PhoenixContact,Ltd.)
ConductorSize AWG16to14
TerminalModelNumber VTUB-2orNTUB-2(J.S.T.Mfg.Co.,Ltd)
Caution
•Whenpeeling offthe sheathofthe cable,takecare nottodamage
otherportions.
•Whencrimping the ferrule, sufciently check the status of theferrule
andcable.Iftheconductorsofthecablestickoutfromtheinsulation
coverorprotrudeexcessivelyfromthetipoftheferrule,accidentssuch
asanelectricshockandrefromashortcircuitmayresult.
①
②
③
A
A>B
1 mm or more
B
①
②
A
A≧B A≦B+C
B C