How to use different-diameter-tube joint (supplied)
1) When using with single connection
•OutdoorPZ3andPZH3series(Type60)
Liquid tube (ø6.35)
Connect the gas socket tube A (ø12.7 - ø15.88)
to the gas tubing side indoor unit
Connect the liquid socket tube B (ø6.35 - ø9.52)
to the liquid tubing side indoor unit
Gas tube (ø12.7)
The following examples show the multiple connections.
Connectable or disconnectable units vary depending on a series of outdoor units. Refer to
the installation instructions for the outdoor unit as well.
Two, three or four indoor units can be operated simultaneously with a single remote controller.
Note that individual operation is not possible.
Master unit and slave unit can be set automatically in twin, triple and double twin system.
No address setting is necessary.
5-2. Connecting Tubing Between Indoor and Outdoor Units
(1) Tightly connect the indoor-side refrigerant tubing extended from the wall with the outdoor-side
tubing.
Indoor Unit Tubing Connection
Unit : mm
Indoor unit type S-25, 36, 50PY3E S-60PY3E
Gas tube ø12.7 ø15.88 (ø12.7)
Liquid tube ø6.35 ø9.52 (ø6.35)
Different-diameter-tube joint for the indoor unit tubing connection part is supplied with
S-60PY3E.
The size of parenthesis indicates the connection tube diameter when using the different-
diameter-tube joint.