75
12. CHECK OF DENSITY LIMIT
The refrigerant (R32), which is used in the air conditioner, is a flammable refrigerant. So the 
requirements for installation space in each room of appliance are determined according to the 
refrigerant charge amount [m
c
] used in the appliance.
Regarding the refrigerant charge amount [m
c
] used in the appliance, refer to the installation 
instructions for the outdoor unit.
The minimum indoor floor space compared with the amount of refrigerant is roughly as follows:
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
2.01.51.00.50.0 3.0 4.02.5 3.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 8.54.5
1.22
7.90
   
   
Cannot be installed
Can be installed
[m
c
] : the refrigerant charge amount (k
g
)
[Amin] :  minimum indoor floor space (m
2
)
[m
c
]  :  The refrigerant charge amount (kg) (Total of refrigerant at shipment and refrigerant 
charge amount in the field).
[Amin] : Minimum indoor floor space (m
2
)
[m
c
] [Amin]
1.22 2.5
1.3 2.6
1.4 2.8
1.5 3.0
1.6 3.2
1.7 3.4
1.8 3.6
1.9 3.8
2.0 4.0
2.1 4.2
2.2 4.4
2.3 4.6
2.4 4.8
2.5 5.0
2.6 5.2
2.7 5.4
2.8 5.6
[m
c
] [Amin]
2.9 5.8
3.0 6.0
3.1 6.2
3.2 6.5
3.3 6.9
3.4 7.4
3.5 7.8
3.6 8.3
3.7 8.7
3.8 9.2
3.9 9.7
4.0 10.2
4.1 10.7
4.2 11.2
4.3 11.8
4.4 12.3
4.5 12.9
[m
c
] [Amin]
4.6 13.4
4.7 14.0
4.8 14.6
4.9 15.2
5.0 15.9
5.1 16.5
5.2 17.2
5.3 17.8
5.4 18.5
5.5 19.2
5.6 19.9
5.7 20.6
5.8 21.3
5.9 22.1
6.0 22.8
6.1 23.6
6.2 24.4
[m
c
] [Amin]
6.3 25.2
6.4 26.0
6.5 26.8
6.6 27.6
6.7 28.5
6.8 29.3
6.9 30.2
7.0 31.1
7.1 32.0
7.2 32.9
7.3 33.8
7.4 34.7
7.5 35.7
7.6 36.6
7.7 37.6
7.8 38.6
7.9 39.6