62
9-9. Checking the Indoor Unit Addresses
Use the remote controller to check the indoor unit address.
CZ-RTC5B (High-spec wired remote controller)
(1)   Keep pressing the 
 ,   and   buttons 
simultaneously for 4 or more seconds. 
The “Maintenance func” screen appears on the LCD 
display.
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4. Test run
Sel. Page [ ] Confirm
20:30 (THU)
(2)   Press  the   or   button to see each menu.
If you wish to see the next screen instantly, press the 
 or   button.
Select “7. Simple settings” on the LCD display and 
press the 
 button.
(3)   The “Simple settings” screen appears on the LCD 
display.
Select the “Unit no.” by pressing the 
 or   
button for changes.
* The initial display is “ALL”.
The indoor unit fan operates only at the selected 
indoor unit.
(4)   Press  the 
 button and select “YES” to restart.
20:30 (THU)
START
[ ]
Maintenance func
5. Sensor info.
6. Servicing check
8. Detailed settings
Sel. Page [ ] Confirm
20:30 (THU)
7. Simple settings
Simple settings
Unit no. Code no. Set data
01
ALL 0001
Sel. Next
20:30 (THU)
9-8. How to Set Refrigerant System Address (Only outdoor PZ2 and PZH2 
series)
●
   Turn on the power in the indoor and outdoor units of the refrigerant system 1.
●
   Switch the power on and wait at least 1 minute and 30 seconds or more. Short-circuit the 
auto address pin of the outdoor unit with turned on and release. (LED1 and LED2 of the 
outdoor unit control PCB blink alternately and the address setting of the indoor unit is started. 
When completed, LEDs go off.)
  <It takes about 10 minutes until it finished.> 
  Auto address pin: If you once again short-circuit the auto address pin before completion 
when the auto address started, the auto address will stop.
●
  Turn on the different refrigerant system’s indoor and outdoor units and wait at least 1 minute 
and 30 seconds or more. Then short-circuit the auto address pin of the outdoor unit and 
release.
●
  Repeat the same procedure and complete the auto address setting of each system.
●
  When the address setting is completed, wait at least 1 minute and 30 seconds or more. Then 
start the operation.
01_330918_EU_Eng.indb   62 2021/9/9   11:27:00