70
Work List No. Content Check
 
□
Possibility of Failure & Checkpoint
Installation
1
Are the indoor units installed following the 
content of Section “2. SELECTING THE 
INSTALLATION SITE”?
□
There is a possibility of light injure or loss of 
property.
Tubing & 
Wiring
2
In the case of multiple installation: Is there 
a wrong tubing connection with another 
system?
□
The unit is inoperated or the refrigerant flows 
into the inoperative unit and the leakage is 
expected. Check if there is a wrong tubing or wiring 
connection with another system.
3
In the case of multiple installation: Is there 
a wrong wiring connection with another 
system?
□
4
Is the earth leakage circuit breaker 
(all-pole switching function provided) 
installed?
□
Power failure or short circuit may cause electric 
shock or fire. Check installation work and ground 
wire work.
5
Is there any wrong installation of optional 
parts or wrong wiring?
□
6
Was the ground wire work performed?
□
7
Are there any wrong power supply wiring, 
wrong connection wire, wrong signal wire 
or loose screw?
□
8
Is the thickness of wire in accordance with 
rule?
□
9
Is the power-supply voltage equal to the 
nameplate of the unit?
□
10
Was the check of the airtight test, flared 
tube fitting and gas leakage on the 
welded portion performed?
□
If the gas leakage occurs, the unit quality not only 
becomes inferior but affects environment. Repair it 
as quickly as possible.
Drain 
Check
11
Has the adhesive been applied to the 
drain connecting portion (resin portion) of 
the indoor unit?
□
The resin portion cracks after a few months and it 
may cause water drain.
12
Is there water leakage?
□
Since there is a possibility of water drain, repair the 
drain pipe if the drain failure or water drain occurs.
13
Indoor unit drain pipe has a downward 
gradient (1/100 or more) by rule. Is the 
drain water flowing smoothly?
□
Heat 
Insulation
14
Was the heat insulation work at a suitable 
location including the flared tube fitting 
(refrigerant tube & drain pipe) performed 
properly?
□
The quality of unit not only becomes inferior but 
there is a possibility of the water drain. So, perform 
the heat insulation work properly.
Test Run
15
Did the abnormal sound occur?
□
Check if there is a fan contact or distortion of the 
indoor unit.
16
Did the cool and warm airflow discharge 
from the indoor unit?
□
Check if the unit does not operate or there is a 
wrong tubing or wiring connection with another 
system.
10. CHECKLIST AFTER INSTALLATION WORK