78
Abnormal 
display
Wireless remote 
controller 
receiver display
Alarm contents Error location
Operation
Timer
Standby
Outdoor Unit
L04
Operating 
and standby 
lamps blinking 
simultaneously
Duplication of outdoor unit address •Checktheindoor/outdoorcontrolline*
L10 Outdoor unit capacity is not set or setting error
•ReplacetheoutdoorunitEEPROM
•Capacityvaluere-setting
L13
Indoor unit type setting error
Ty pe of indoor / outdoor units is different
•ReplacetheindoorunitEEPROM
•ChecktheoutdoorunitcontrolPCB
•CheckthetypeofIUandOU,andre-setaddress
L18 4-way valve locked trouble / operation failure
•Checkthe4-wayvalve
•Checkthe4-wayvalvewiring
•ChecktheoutdoorunitcontrolPCB
P03
Operating 
and standby 
lamp blinking 
alternately
Compressor discharge temperature trouble
•Checktherefrigerantcycle(gasleak)
•Troublewiththeelectronicexpansionvalve
•Checkthedischargetemperaturesensor(TD)
P04
Condensing pressure trouble 
Compressor discharge pressure trouble
•Checktherefrigerantcycle
•Valveblockage
•Heatexchangerobstruction
P05
Open phase detected
AC power supply trouble
•Checkthepowersupply
•Checkthereactorwiring
•ChecktheoutdoorunitcontrolPCB
•Checkthecompressorwiring
P07 HIC (IPM) temperature trouble
•ChecktheoutdoorunitcontrolPCB
•ChecktheHIC
•Compressorlocked
•Valveblockage
P13
Timer and 
standby 
lamp blinking 
alternately
Valve error 
Refrigerant circuit error
Wrong installation for refrigerant piping and wiring
•Valveblockage
•Checktherefrigerantcircuit
•Checktherefrigerantpipingandwiringinstallation
P14 O
2
 sensor detected •InputfromtheO
2
 sensor
P15
Operating 
and standby 
lamp blinking 
alternately
Insufficient gas level detected
•Checktherefrigerantcycle(gasleak)
•Troublewiththeelectronicexpansionvalve
•Valve(orrefrigerantcircuit)blockage
P16 Compressor overcurrent trouble
•Layershortonthecompressor
•Compressorlocked
•ChecktheoutdoorunitcontrolPCB
P22
Outdoor unit fan motor trouble
Outdoor unit fan trouble
•Checktheoutdoorunitfanmotor,connector
•ChecktheoutdoorunitcontrolPCB
P29 Inverter compressor trouble
•Layershortonthecompressor
•ChecktheoutdoorunitcontrolPCB
•Checktheinvertercompressorwiring(Openphase/
Reverse phase)
•Compressoractuationfailure(includelock)
•Valve(orrefrigerantcircuit)blockage
P31 Indoor unit in group control trouble •Repairindoorunitwhichblinkingalarm
ON:    Blinking:    OFF: 
* 3-Line  :  Connection cable between outdoor and indoor unit
  2-Line  :  Inter-unit control wiring