4-4 Calibration and Start-Up
DC590+ DRV Series DC Digital Drive
Keypad Description
Press Display
Now navigate to the following parameters and use the
M
,
and
E
keys, as above, to enter your values.
CONFIGURE DRIVE
NOM MOTOR VOLTS
* Enter the motor nameplate voltage
CONFIGURE DRIVE
ARMATURE CURRENT
* Enter the motor nameplate armature current
CONFIGURE DRIVE
FIELD CURRENT
* Enter the motor nameplate field current
CONFIGURE DRIVE
FLD. CTRL MODE
Verify set to VOLTAGE CONTROL
CONFIGURE DRIVE
FLD. VOLTS RATIO
Calculate and enter ratio where
FLD. VOLTS RATIO = (Motor Nameplate Field Volts ÷ AC Supply ) × 100
For example, 300 VDC ÷ 460 VAC × 100 = 65%
CONFIGURE DRIVE
SPEED FBK SELECT
Verify set to ARMATURE VOLTS when first installing the drive
CONFIGURE DRIVE
ENCODER LINES
- Skip if not using an encoder -
Enter the encoder pulses per revolution (PPR) rating
CONFIGURE DRIVE
ENCODER RPM
- Skip if not using an encoder -
Enter the process maximum speed; corresponds to 100% speed
CONFIGURE DRIVE
CONFIGURE ENABLE
Set to DISABLED. The drive will start calibrating, indicated by the display: CONFIGURE
DRIVE::CALIBRATING